2007-04-15 15:48:27 | ********* UNSAT 2ND REVIEW *********** |
| |
| 1) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| CODES REQUIRED TO BE STATED ON PLANS FOR PROJECT. THESE |
| WERE ADDED TO ELECTRICAL SHEETS; HOWEVER CODES COULD |
| NOT BE LOCATED ON ARCHITECTURAL SHEETS. |
| FBC 106.1.2 |
| FBC 2004 W/2006 REVISIONS |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE BE SURE THE TITLE BLOCKS FOR THE |
| ARCHITECTURE FIRM AS LICENSED THROUGH THE STATE |
| CONTAINS THE PRINTED FIRM CERTIFICATE OF AUTHORIZATION |
| NUMBER ON ALL SHEETS WHICH CONTAIN THE FIRM. |
| ON ANY SHEETS WHICH DO NOT NEED TO BE REPLACED, THIS |
| MAY BE HAND PRINTED OR STAMPED ON SHEETS. |
| FAC 61G1-16.004, FS481.219 *SEE ATTACHED PRINT OUT FROM |
| THE STATE OF FLORIDA. |
| |
| 3) NOTE: PLEASE SEE THE MINIMUM CLEARANCES FOR THE A/C |
| CU DISCONNECTS DOES NOT MEET 110.26 |
| |
| 4) NOTE: PLEASE CLARIFY THE LOCATION OF WATER HEATER |
| AND SEPARATION FROM COMBUSTIBLES PER 422.17 |
| |
| 5) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER |
| HEATER MUST BE FIGURED INTO LOAD CALCULATIONS AT 125%. |
| |
| 6) NOTE: PLEASE SEE THE NEW SERVICE AS SHOWN MUST HAVE |
| THE GROUNDING ELECTRODE CONDUCTOR CONTINUOUS TO FOOTER |
| STEEL WITH ALL ITEMS AS SHOWN ON GROUNDING RISER PER |
| 250.66 |
| SHOWS #4, WHEN THIS SHOULD BE THE #2. 250.64C 250.66C |
| IS USED WHEN THE SOLE CONNECTION. |
| PLEASE CLARIFY ANY METALLIC COLD WATER PIPE ? |
| |
| 7) NOTE: PLEASE SEE CODE SECTIONS FOR LOAD CALCULATIONS |
| FOR EACH ARE FROM THE 2002 NEC. |
| PLEASE ADJUST TO THE 2005 NEC. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |