Plan Review Notes
Plan Review Notes For Permit 07020336
Permit Number 07020336
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-15 15:48:27********* UNSAT 2ND REVIEW ***********
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 CODES REQUIRED TO BE STATED ON PLANS FOR PROJECT. THESE
 WERE ADDED TO ELECTRICAL SHEETS; HOWEVER CODES COULD
 NOT BE LOCATED ON ARCHITECTURAL SHEETS.
 FBC 106.1.2
 FBC 2004 W/2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE BE SURE THE TITLE BLOCKS FOR THE
 ARCHITECTURE FIRM AS LICENSED THROUGH THE STATE
 CONTAINS THE PRINTED FIRM CERTIFICATE OF AUTHORIZATION
 NUMBER ON ALL SHEETS WHICH CONTAIN THE FIRM.
 ON ANY SHEETS WHICH DO NOT NEED TO BE REPLACED, THIS
 MAY BE HAND PRINTED OR STAMPED ON SHEETS.
 FAC 61G1-16.004, FS481.219 *SEE ATTACHED PRINT OUT FROM
 THE STATE OF FLORIDA.
  
 3) NOTE: PLEASE SEE THE MINIMUM CLEARANCES FOR THE A/C
 CU DISCONNECTS DOES NOT MEET 110.26
  
 4) NOTE: PLEASE CLARIFY THE LOCATION OF WATER HEATER
 AND SEPARATION FROM COMBUSTIBLES PER 422.17
  
 5) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER
 HEATER MUST BE FIGURED INTO LOAD CALCULATIONS AT 125%.
  
 6) NOTE: PLEASE SEE THE NEW SERVICE AS SHOWN MUST HAVE
 THE GROUNDING ELECTRODE CONDUCTOR CONTINUOUS TO FOOTER
 STEEL WITH ALL ITEMS AS SHOWN ON GROUNDING RISER PER
 250.66
 SHOWS #4, WHEN THIS SHOULD BE THE #2. 250.64C 250.66C
 IS USED WHEN THE SOLE CONNECTION.
 PLEASE CLARIFY ANY METALLIC COLD WATER PIPE ?
  
 7) NOTE: PLEASE SEE CODE SECTIONS FOR LOAD CALCULATIONS
 FOR EACH ARE FROM THE 2002 NEC.
 PLEASE ADJUST TO THE 2005 NEC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]