2007-03-12 08:13:26 | DENIED |
| REFERENCE: FBC-2004 W/2006 AMENDMENTS |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. PLEASE INDICATE CODE REFERENCES ON PLANS. SECTIONS |
| 106.1.1 & 106.1.2. |
| |
| 2. SHT 2 OF 6A INDICATES 3" DUAL RPZV BACKFLOW |
| PREVENTERS ON 4" DIP WATER LINE. PER TABLE 603.1(D), |
| ALL BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE |
| AS THE LINE IN WHICH THEY ARE INSTALLED.4" DUAL RPZV |
| BACKFLOWS ARE REQUIRED. |
| |
| 3. SHTS A103 & P-3.SHT A103 SHOWS NO EMERGENCY |
| OVERFLOW SCUPPER FOR AREA #4 OF THE ROOF, BUT SHT P-3 |
| INDICATES AN OVERFLOW SCUPPER. PLEASE CORRELATE |
| INFORMATION ON THESE TWO SHEETS. SECTION 106.1.1. |
| |
| 5. SHT P-5 WATER RISER DIAGRAMS DO NOT REFLECT THE |
| FLOOR PLAN FOR THE REF. & THE WATER SERVICE ROUTING FOR |
| BOTH UNITS. PLEASE CORRELATE. SECTION 106.1.1.- WATER |
| RISER DIAGRAM FOR UNIT "B' DOES NOT REFLECT THE FLOOR |
| PLAN AT THE 3RD FLOOR MASTER BATH AND BATH #2. OVERHEAD |
| PIPING ON THE FLOOR PLAN IS SHOWN TO THE RIGHT OF THE |
| W/CAND TUB, AND NO SHOWER IS INDICATED ON THE FLOOR |
| PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 6. SUBMIT A HORIZONTAL STORM RISER ISOMETRIC RISER, AND |
| VERTICAL STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES, AND |
| INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| SYSTEM. SECTION 106.3.5.1.3(7)(13) & TABLE 1106.3. |
| |
| 7. SHT IR-1 IRRIGATION PLANS ARE INCOMPLETE. SHOW ALL |
| PIPING AND INDICATE PIPE SIZE. SHOW THE LOCATION OF THE |
| METER, BACKFLOW PREVENTER, & RAIN SENSOR. SECTION |
| 106.1.1. |
| |