Plan Review Notes For Permit 07020336 |
Permit Number |
07020336 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-15 14:34:25 | --------------DENIED---------------- | | | | FBC 2004 W/ 2006 REVISIONS | | FRC 2004 | | FBC,M 2004 | | | | 1. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL | | BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M | | 1107.2.1 | | | | 2.. PG AC-3 UNITS A & B, 3RD FLOOR SHOWS TWO 4" ROUND | | DRYER EXHAUST DUCTS TERMINATING AT ROOF. ROOF PLAN | | SHOWS NO DRYER EXHAUST TERMINATIONS. PLEASE CLARIFY. | | FBC 106.1.1 | | | | 3. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES OF | | ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT | | REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M | | TABLE 401.6 AND FRC M1501.1 | | | | 4. PLEASE SHOW THE SIZE OF ALL DUCTS BETWEEN TRANSFER | | GRILLS. FBC 106.1.1 | | | | 5. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM | | THAT IS IN COMPLIANCE WITH FRC 1411.3.1 | | | | 6. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS | | ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1, | | FBC TABLE 13-610.1.ABC.2.1 | | | | 7. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC 2004 | | W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT AND | | RESUBMIT. | | | | IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE | | DO NOT HESITATE TO CONTACT ME. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|