2007-03-15 14:34:25--------------DENIED----------------
  
 FBC 2004 W/ 2006 REVISIONS
 FRC 2004
 FBC,M 2004
  
 1. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL
 BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M
 1107.2.1
  
 2.. PG AC-3 UNITS A & B, 3RD FLOOR SHOWS TWO 4" ROUND
 DRYER EXHAUST DUCTS TERMINATING AT ROOF. ROOF PLAN
 SHOWS NO DRYER EXHAUST TERMINATIONS. PLEASE CLARIFY.
 FBC 106.1.1
  
 3. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES OF
 ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT
 REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M
 TABLE 401.6 AND FRC M1501.1
  
 4. PLEASE SHOW THE SIZE OF ALL DUCTS BETWEEN TRANSFER
 GRILLS. FBC 106.1.1
  
 5. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM
 THAT IS IN COMPLIANCE WITH FRC 1411.3.1
  
 6. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS
 ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1,
 FBC TABLE 13-610.1.ABC.2.1
  
 7. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC 2004
 W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE
 DO NOT HESITATE TO CONTACT ME.
  