Plan Review Notes
Plan Review Notes For Permit 07020332
Permit Number 07020332
Review Stop G
Sequence Number 1
Notes
Date Text
2007-02-22 09:17:10DENIED
 REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS; CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: ON THE RESUBMITTED DRAWING PLEASE SHOW THE ENTIRE
 GAS SYSTEM ON THE ISOMETRIC (NOT CUT SECTIONS) FROM THE
 METER TO THE MOST REMOTE OUTLET IN THE BUILDING. PER
 FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. WITH THE GIVEN INFOMATION ON THE SUBMITTED DRAWINGS
 THE LONGEST LENGTH OF THE SYSTEM IS 60'. PLEASE NOTE
 THE RED LINED CORRECTIONS OF THE CSST IN THE ATTIC AND
 THE PE TO THE POOL HEATER. PLEASE CORRECT PER FBC-2004
 FUEL GAS TABLES 402.4(14) CSST AND 402.4(20) PE. PLEASE
 REFERENCE THE ATTACHED FUEL GAS TABLES INDICATING THE
 REQUIRED CHANGES. PLEASE CORRECT AND RESUBMIT.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  