2007-03-23 15:04:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE ANCHORING SPECIFIED, 8", IS NOT COMPLIANT FOR
 HOLLOW BLOCK, STORM PANELS, PAGE 3.YOU HAVE
 HIGHLIGHTED CONCRETE SUBSTRATE BUT THE SCHEDULE STATES
 THAT THIS IS CBS.
  
 2.)IT IS DIFFICULT TO READ THE PRODUCT APPROVAL, BUT
 IT APPEARS THAT THE ACCORDION SHUTTERS REQUIRE ANCHOR
 SPACING OF 7" AND 5", TOP AND BOTTOM, INSIDE MOUNT IF
 THE SUBSTRATE IS CONCRETE.INSIDE MOUNT IS APPARENTLY
 NOT ALLOWED FOR CBS.PLEASE ADDRESS.
  
 3.)THE ACCORDION PRODUCT APPROVAL IS ILLEGIBLE.
 PLEASE PROVIDE LEGIBLE DOCUMENTS.
  
 4.)WHEN MARKING DETAILS,PLEASE USE INK RATHER THAN A
 HIGHLIGHTER AS HIGHLIGHTER DOES NOT APPEAR WHEN
 SCANNED.NOTE THAT I WOULD HAVE MARKED THE DETAILS IN
 INK FOR YOU HAD THIS PLAN BEEN CODE COMPLIANT.
  