Plan Review Notes
Plan Review Notes For Permit 07020267
Permit Number 07020267
Review Stop P
Sequence Number 6
Notes
Date Text
2008-12-01 12:17:11REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. OK
 2. OK
  
 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR
 SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR
 INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT
 TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE
 BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2.
 A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK.
 SECTION 901.2.1.
 ****RESPONSE NOTED, BUT THE FLOOR PLAN AND SANITARY
 RISER DIAGRAM STILL SHOW THE DRAIN FOR THE ICE MACHINE
 AS A FLOOR DRAIN. A FLOOR SINK IS REQUIRED FOR INDIRECT
 WASTE. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS.
  
 ***********NEW COMMENT**********
  
 1B. A RELIEF VENT IS REQUIRED FOR THE AIR ADMITTENCE
 VALVE INDICATED ON THE NEW S-4 SINK. SECTION 917.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  