2008-08-28 09:24:23 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| |
| 1. SHT 3 OF 4. A WATER HAMMER ARRESTOR IS REQUIRED ON |
| THE WATER SUPPLY LINE TO THE ICE MAKER. SECTION 604.9 & |
| PDI-WH 201. |
| |
| 2. SHT 3 OF 4. THE NEW S-4 SINK DRAIN SHALL NOT DRAIN |
| THRU THE HORIZONTAL WET VENT FOR THE TOILET ROOM |
| FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE DOWNSTREAM |
| OF THE HORIZONTAL WET VENT. SECTION 909.1. SINK SHALL |
| CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES. |
| |
| 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR |
| SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR |
| INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT |
| TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE |
| BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2. |
| A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK. |
| SECTION 901.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |