Plan Review Notes For Permit 07020267
Permit Number 07020267
Review Stop P
Sequence Number 5
Notes
Date Text
2008-08-28 09:24:23REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT 3 OF 4. A WATER HAMMER ARRESTOR IS REQUIRED ON
 THE WATER SUPPLY LINE TO THE ICE MAKER. SECTION 604.9 &
 PDI-WH 201.
  
 2. SHT 3 OF 4. THE NEW S-4 SINK DRAIN SHALL NOT DRAIN
 THRU THE HORIZONTAL WET VENT FOR THE TOILET ROOM
 FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE DOWNSTREAM
 OF THE HORIZONTAL WET VENT. SECTION 909.1. SINK SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES.
  
 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR
 SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR
 INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT
 TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE
 BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2.
 A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK.
 SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]