2008-09-09 08:15:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLANS M-1 AND M-2. | | *** DENIED *** | | | | 1) MECHANICAL PLAN M-2 EQUIPMENT SCHEDULE A/C SYSTEM #1 | | IS A 9.95 EER. PER 2004 FBC 13-407.1.ABC.3.2A (TABLE) | | THE MINIMUM EER IS 10.3 FOR THIS SIZE SYSTEM. PLEASE | | CORRECT. | | | | 2) THE COOLING LOAD CALCULATIONS WILL NEED TO BE | | REVISED AS THE COOLING ZONES HAVE CHANGED, PER 2004 FBC | | 13-407.1.ABC.1 AND 13-407.1.ABC.1.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|