2008-09-09 08:15:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS M-1 AND M-2.
 *** DENIED ***
  
 1) MECHANICAL PLAN M-2 EQUIPMENT SCHEDULE A/C SYSTEM #1
 IS A 9.95 EER. PER 2004 FBC 13-407.1.ABC.3.2A (TABLE)
 THE MINIMUM EER IS 10.3 FOR THIS SIZE SYSTEM. PLEASE
 CORRECT.
  
 2) THE COOLING LOAD CALCULATIONS WILL NEED TO BE
 REVISED AS THE COOLING ZONES HAVE CHANGED, PER 2004 FBC
 13-407.1.ABC.1 AND 13-407.1.ABC.1.1.
  