2007-03-31 11:22:37 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 2ND |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| 2)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)OK |
| |
| 4)OK |
| |
| 5) OK |
| |
| 6)FBC 11-7.2(2) (I) A PORTION OF THE MAIN COUNTER |
| WHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE |
| PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.IN NEW |
| CONSTRUCTION, WHERE THE SELLING SPACE IS UNDER 5,000 |
| SQUARE FEET, ONLY ONE CHECK-OUT AISLE IS REQUIRED TO BE |
| ACCESSIBLE. SHOW COMPLIANCE WITH ELEVATION DRAWINGS. |
| |
| 6A)11-2.2 EQUIVALENT FACILITATION. |
| DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING |
| REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS |
| AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE |
| DESIGNS AND TECHNOLOGIES USED WILL PROVIDE |
| SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND |
| USABILITY OF THE FACILITY. SHOW THE WHEELCHAIR TURNING |
| SPACE IN OFFICE #2. SEE FBC.CH.11 FIG #3. |
| |
| 7)FBC.11-5.2 WHERE FOOD OR DRINKIS SERVED AT |
| COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION |
| BY COUSTOMERS SEATED ON STOOLS OR STANDING AT THE |
| COUNTER, A PORTION OF THE MAIN COUNTERWHICH IS60 |
| INCHES IN LENGTH MINIMUM SHALL BE PROVIDED IN |
| COMPLIANCE WITH SECTION 11-4.32 OR SERVICES SHALL BE |
| AVAILABLE AT TABLES WITHIN THE SAME AREA. |
| |
| 7A)FBC. 11-4.33.3AT LEAST ONE COMPANION FIXED SEAT |
| SHALL BE PROVIDED NEXT TO EACH WHEEL CHAIR SEATING |
| AREA. SHOW COMPLIANCE WITH ELEVATION DRAWINGS. ALSO |
| SHOW THE ELEVATION DETAILS OF THE TABLE PROVIDED. SEE |
| FIG.45. |
| |
| |
| 8)OK |
| |
| 9)SHOWER STALLS SHALL COMPPLY WITH SECTION 11-4.21 |
| PROVIDE AN ELEVATION DRAWINGS WITH ALL THE |
| DIMENTIONS............ |
| OK, BUT SHOWER #2 IS MISSING THE DIMENTIONS. COMPLY AND |
| SHOW DIMENTIONS. ALSO INDICATE THE TYPE OF |
| MATERIALWHICH WILL BE USED FOR THE GRAB BARS BACKING |
| AND THE 250 LBSREQUIREMENT OF SECTION 11-4.26.3. |
| |
| 10)OK |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |