Plan Review Notes For Permit 07020267 |
Permit Number |
07020267 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-15 10:26:30 | DENIED; | | 1. PLUMBING FIXTURE SCHEDULE, TOILETS TO BE ELONGATED | | TYPE (NOT SURE OF MODEL NUMBER) AND SEAT TO BE OPEN | | FRONT. SEE FBC PLUMBING SECTIONS, 420.2 AND 420.3. | | 2. PLUMBING NOTE # 12; SEE SECTION 410.1. THE ONLY | | EXCEPTION FOR NOT INSTALLING A DRINKING FOUNTAIN IS FOR | | A RESTAURANT. DRINKING FOUNTAIN IS REQUIRED , SEE TABLE | | 403.1 (2B). | | 3. PLUMBING NOTE # 8; PVC PIPE CAN ONLY BE USED 5' INTO | | A BUILDING 605.3. SEE TABLE 605.4 FOR TYPE OF MATERIAL | | THAT CAN BE USED. | | 4. PAGE 1 FLOOR PLAN NOTE #16;SHOW A DETAIL WITH ALL | | REQUIRED MEASUREMENTS TO MEET HANDICAP REQUIREMENTS | | PER. FBC-2004 BUILDING CHAPTER 11. SEE SECTION | | 11-4.24.2 THRU 11-4.24.7. | | 5. SANITARY RISER DIAGRAM; | | A) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO | | BE 3" SECTION 406.3. | | B)FLOOR DRAIN IN WORK ROOM NOT VENTED AND | | SHOULD HAVE A TRAP PRIMER. | | C) F/D IN WOMAN'S ROOM NOT VENTED. | | D) F/D IN WOMAN'S SHOWER ROOM NOT VENTED. | | E) F/D IN MEN'S ROOM MISSING. | | F) F/D MEN'S SHOWER ROOM NOT VENTED. | | 6. WATER RISER DIAGRAM; AUTOMATIC CLOTHES WASHER | | REQUIRE WATER HAMMER ARRESTORS, TOBE INSTALLED PER | | MANUFACTURE INSTALLATION INSTRUCTIONS. SEE SECTION | | 604.9. | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 805-6695 |
|