2007-02-15 13:48:37*** DENIED ***
 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) AS THE CLOTHS DRYER VENT IS OVER 25 FEET, PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE CLOTHS DRYER.
  
 3) SEE MECHANICAL PLANS PAGE M-1, EF-5 NEEDS TO BE 50
 CFM'S., SEE 2004 FBC/M TABLE 403.3 PUBLIC SPACES,
 SHOWER ROOM, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.