2007-02-15 16:31:20 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. FBC 2004 WITH 2006 REVISIONS |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| ------------------------------------- |
| ) NUMBER OF UNITS |
| ) NUMBER OF FLOORS |
| ) NUMBER OF ROOMS |
| ) SQ. FT. FOOTPRINT |
| ) SQ. FT. UNDER ROOF (TOTAL) |
| ) OCCUPANT LOAD |
| ) FLOOD ZONE |
| ) FLOOD ELEVATION |
| )L.O.M.R. |
| |
| 4)THE VALUE ON THE APPLICATION IS LOW.108.3*IF, |
| IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| VALUATION OF BUILDING, ALTERATION. STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; |
| EXCLUDING LAND ONLY. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS |
| SERVICES. |
| |
| 5)FBC 106.3.5.1.1SUBMIT A LIFE SAFETY PLAN SHOWING |
| THE MEANS OF EGRESS AND TRAVEL DISTANCE. IS THERE A |
| SPRINKLER SYSTEM IN THIS AREA?CLARIFY. |
| |
| 6)FBC 11-7.2(2) (I) A PORTION OF THE MAIN COUNTER |
| WHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE |
| PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.IN NEW |
| CONSTRUCTION, WHERE THE SELLING SPACE IS UNDER 5,000 |
| SQUARE FEET, ONLY ONE CHECK-OUT AISLE IS REQUIRED TEO |
| BE ACCESSIBLE. SHOW COMPLIANCE WITH ELEVATION |
| DRAWINGS. |
| |
| 7)FBC.11-5.2 WHERE FOOD OR DRINKIS SERVED AT |
| COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION |
| BY COUSTOMERS SEATED ON STOOLS OR STANDING AT THE |
| COUNTER, A PORTION OF THE MAIN COUNTERWHICH IS60 |
| INCHES IN LENGTH MINIMUM SHALL BE PROVIDED IN |
| COMPLIANCE WITH SECTION 11-4.32 OR SERVICES SHALL BE |
| AVAILABLE AT TABLES WITHIN THE SAME AREA. |
| |
| 8)CLARIFY IF THE BUILDING OR NEW SPACE HAS A |
| SPRINKLER SYSTEM, AND IF IT DOES, STATE THE TYPE OF |
| SPRINKLER SYSTEM ON THE DRAWINGS. SEE SHEET 1. |
| |
| 9)SHOWER STALLS SHALL COMPPLY WITH SECTION 11-4.21 |
| PROVIDE AN ELEVATION DRAWINGS WITH ALL THE DIMENTIONS. |
| |
| 10)FBC 1210.3 SHOWER COMPARTMENTS AND WALLS ABOVE |
| BATHBUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED |
| WITH A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT |
| LESS THAN 70 INCHES ABOVE THE DRAIN INLET. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |