Plan Review Notes For Permit 07020266 |
Permit Number |
07020266 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2008-09-11 09:02:45 | | | | | | | | | ** DENIED REVIEW OF REVISION** | | | | | | | | 1) NOTE: PLEASE SEE FBC 13-101.1 AS THE METHOD *A* | | SUBMITTED MAY NOT BE USED. THIS IS NOT A WHOLE | | BUILDING. | | | | 2) NOTE: PLEASE SEE REVIEW NOTES FROM 6/13/08 WHICH ARE | | STILL IN NEED OF ADDRESSING. THESE WILL BE ATTACHED. | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|