2008-06-13 16:29:50 | ** DENIEDREVISION** |
| |
| 1) NOTE: PLEASE BE SURE ALL CIRCUITING IS SHOWN ON |
| PLANS AND COORDINATE WITH THE SUBMITTED PANEL |
| SCHEDULES. |
| PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS |
| AND EXIT LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO |
| THE LOCAL LIGHTING IN ANY ONE AREA. |
| PLEASE SEE MANY OF THESE SHOWN ON PLANS DO NOT CONTAIN |
| ANY CIRCUITING. |
| PLEASE BE SURE TO SUBMIT REVISE LIGHTING PLANS ALSO AND |
| COORDINATE WITH PANEL SCHEDULES. |
| PLEASE BE SURE TO REVISE ANY LIGTHING PERFORMANCE |
| CALCULATIONS FOR ANY REVISED LIGTHING SINCE PERMIT |
| ISSUED PLANS WERE DONE. |
| |
| 408.4, 310.16, 240.4, 700.12F,ETC |
| 13-415.2.ABC.1.1, .1.2, 13-415.2. |
| FBC 106.1.2, 106.3.5.1.2, 106.5 FOR ADDITIONAL |
| INFORMATION, COORDINATION AND RECORDS RETENTION. |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |