Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop E
Sequence Number 6
Notes
Date Text
2008-06-13 16:29:50** DENIEDREVISION**
  
 1) NOTE: PLEASE BE SURE ALL CIRCUITING IS SHOWN ON
 PLANS AND COORDINATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS
 AND EXIT LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO
 THE LOCAL LIGHTING IN ANY ONE AREA.
 PLEASE SEE MANY OF THESE SHOWN ON PLANS DO NOT CONTAIN
 ANY CIRCUITING.
 PLEASE BE SURE TO SUBMIT REVISE LIGHTING PLANS ALSO AND
 COORDINATE WITH PANEL SCHEDULES.
 PLEASE BE SURE TO REVISE ANY LIGTHING PERFORMANCE
 CALCULATIONS FOR ANY REVISED LIGTHING SINCE PERMIT
 ISSUED PLANS WERE DONE.
  
 408.4, 310.16, 240.4, 700.12F,ETC
 13-415.2.ABC.1.1, .1.2, 13-415.2.
 FBC 106.1.2, 106.3.5.1.2, 106.5 FOR ADDITIONAL
 INFORMATION, COORDINATION AND RECORDS RETENTION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  