2008-06-09 11:44:37REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 NFPA
  
 1. THE REFERENCE SHEET SHOWING THE ROUTING OF THE VENT
 PIPE IS NOT APPROVED. NFPA 101 SECTION 7.1.3.2.1(6).
 PENETRATIONS INTO, AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ASSEMBLY. PIPING CAN NOT BE ROUTED THRU THE
 STAIRWELL.
  
 2. A RELIEF VENT IS REQUIRED FOR THE AIR ADMITTENCE
 VALVES PER SECTION 917.3.1.
  
 3. SUBMIT AN ELEVATION FOR THE VENT AND AIR INTAKE
 SHOWING ALL DIMENSIONS FROM ALL OPENINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  