Plan Review Notes For Permit 07020266 |
Permit Number |
07020266 |
|
Review Stop |
MEDGAS |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-06-09 11:52:00 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | NFPA | | | | 1. SHT 3 OF 4 INDICATES THE VACUUM EXHAUST TO BE | | TERMINATED OUT THE NORTH WALL. PER SECTION 713.6 THE | | EXHAUST FROM A VACUUM PUMP SERVING A VACUUM (FLUID | | SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR | | ABOVE THE ROOF. | | | | 2. PIPING SHALL NOT BE THRU THE STAIRWELL PER NFPA-101 | | SECTION 7.1.3.2.1(6). PLEASE SHOW THE ROUTING OF THE | | EXHAUST FOR THE VACUUM AND THE INTAKE FOR THE | | COMPRESSOR. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|