Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-06 07:57:112007-07-06 07:57:11
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO
 NOT CORRELATE WITH THE FIXTURE LEGEND ON PLANS. PLEASE
 SEE THE RESPONSE HAND WRITTEN ON NOTES SHEETS MENTIONS
 THE CERTAIN FIXTURES ARE EXEMPT UNDER 13-415.2.B.2,
 HOWEVER PLEASE SEE THIS SECTION OF THE CODE DOES NOT
 APPLY TO THE CALCULATIONS SUBMITTED AND THE USE AS
 SHOWN. PLEASE SEE ADDITIONAL ALLOWANCES ARE PERMITTED,
 HOWEVER THAT DOES NOT MEAN THEY ARE EXEMPT. IN EITHER
 CASE THE SECTION REFERENCED IS FOR SPACE BY SPACE
 CALCULATIONS AND PERFORMANCE MEASURES.
 PLEASE SEE 13-415.1.AB.1.,13-415.1.A, 13-415.2
  
 PLEASE REVISE AND ADJUST.
  
 2) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN
 THE LEFT HADN SIDE OF THE PLANS. THESE WERE REMOVED
 FROM PLANS BY THIS OFFICE ON THIS REVIEW AND PLACED
 INTO TWO PACKAGES FOR EACH.
 FBC106.1
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-06 07:02:042007-07-06 07:02:04
 REVIEW IN PROGRESS
2007-07-05 17:51:502007-07-05 17:51:50
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR THE COMM BOARD ONCE ELECTRICLA
 REVIEW IS DONE.