2007-07-06 07:57:11 | 2007-07-06 07:57:11 |
| ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO |
| NOT CORRELATE WITH THE FIXTURE LEGEND ON PLANS. PLEASE |
| SEE THE RESPONSE HAND WRITTEN ON NOTES SHEETS MENTIONS |
| THE CERTAIN FIXTURES ARE EXEMPT UNDER 13-415.2.B.2, |
| HOWEVER PLEASE SEE THIS SECTION OF THE CODE DOES NOT |
| APPLY TO THE CALCULATIONS SUBMITTED AND THE USE AS |
| SHOWN. PLEASE SEE ADDITIONAL ALLOWANCES ARE PERMITTED, |
| HOWEVER THAT DOES NOT MEAN THEY ARE EXEMPT. IN EITHER |
| CASE THE SECTION REFERENCED IS FOR SPACE BY SPACE |
| CALCULATIONS AND PERFORMANCE MEASURES. |
| PLEASE SEE 13-415.1.AB.1.,13-415.1.A, 13-415.2 |
| |
| PLEASE REVISE AND ADJUST. |
| |
| 2) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN |
| THE LEFT HADN SIDE OF THE PLANS. THESE WERE REMOVED |
| FROM PLANS BY THIS OFFICE ON THIS REVIEW AND PLACED |
| INTO TWO PACKAGES FOR EACH. |
| FBC106.1 |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |