Plan Review Notes For Permit 07020266 |
Permit Number |
07020266 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-05-07 16:29:49 | *****DENIED***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS | | CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY | | REFERENCES 2005 NFPA 101. | | | | 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR | | ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE | | FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE, | | THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO | | LESS THAN 1" IN WIDTH. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT | | WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|