Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-18 18:28:10 
 ** UNSAT2ND REVIEW**
  
  
 1) NOTE: PLEASE COORDINATE ADDRESS. PLEASE SEE THE
 PERMIT APPLICATION STILL CONTAINS THE ADDRESS AND
 PARCEL CONTROL NUMBER (PCN) FOR 600 N. DIXIE WHEN THE
 SCOPE OF WORK IS BEING DONE AT 600 SOUTH DIXIE. PLEASE
 BE SURE TO CHANGE APPLICATION AND OWNER INFORMATION AS
 THE OWNER FOR 600 S DIXIE IS NOT GRAND TRUST BANK.
  
 2) NOTE: PLEASE SEE THAT ALL RAISED SEALS SHALL BE
 CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL
 WHICH IS REQUIRED READABLE.THE INFORMATIONON MOST
 OF THE SEALS ON SHEETS WILL NOT PROVIDE ALL INFORMATION
 ON SEAL EVEN WHEN USING A LEAD RUB NOT APPLIED WITH
 PENCIL.
 PLEASE BE SURE ALL PLANS SHEETS AND ENERGY CALCULATIONS
 ARE SEALED WITH READABLE RAISED SEAL.
 FS 481.221, FAC61G1-16.002,.3
  
 3) NOTE: PLEASE SEE THE NOTE FROM PREVIOUS REVIEW NEEDS
 TO BE CLARIFIED FOR THESE LOCATIONS. A HANDWRITTEN
 RESPONSE MENTIONS THERE IS NO ANESTHETIZING AT THIS
 LOCATION AND TO SEE NOTE #8, HOWEVER NOTE #8 DOES NOT
 SEEM TO CONTAIN ANY MENTIONING OF THIS?
 PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. PLEASE
 SPECIFY AREAS AND USE IN THESE AREAS. PLEASE SPECIFY
 ANY USE OF ANESTHETIZING LOCATIONS IF THIS APPLIES TO
 THIS OFFICE AND USE.
 NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND
 GROUNDING AS REQUIRED.
  
 4) NOTE: PLEASE KNOW THAT IN NOTED RESPONSE FROM
 ARCHITECT WHICH WAS WRITTEN ON THE REVIEW NOTES FROM
 PREVIOUS REVIEW IT MENTIONS "THIS REVIEWER IS GETTING
 TOO PICKY", PLEASE KNOW THAT THIS REQUIREMENT WAS
 ADOPTED INTO THE NEW CODE AND THE TEXT IN THE PREVIOUS
 NOTE WAS EXTRACTED DIRECTLY FROM THE CODE. PLEASE
 CONTACT THE CODE PANELIST FOR ANY ROP'S (REQUEST FOR
 PROPOSALS).
 THIS IS A MINIMUM REQUIREMENT WHICH IS SET FORTH FROM
 NFPA AND NOT THIS OFFICE.
 THIS NOTE WILL REMAIN AS THERE ARE SOME ITEMS ON PLANS
 WHICH MAY NOT INDICATE CIRCUITING AND ITEMS ON PLANS
 WHICH HAVE NOT BEEN CLEARED UP AND CLARIFICATION FOR
 DESIGNER ON WHAT WILL BE REQUIRED FOR PROJECTS REVIEWED
 IN TEH CITY OF WEST PALM BEACH.
  
 (NOTE FROM PREVIOUS REVIEW) PLEASE CORRELATE PANEL
 SCHEDULE AND COMPLETE PANEL SCHEDULE(S) SO THAT ALL
 ITEMS ON PANEL SCHEDULE ARE SPECIFIC TO AREAS AND ROOMS
 IN WHICH THEY FEED. PLEASE SEE COMMENTARY BELOW
 EXTRACTED FROM THE CODE. *SECTION 408.4 WAS REVISED FOR
 THE 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR
 EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD
 BE LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 5) NOTE: PLEASE SEE THIS NOTE REMAINS. IN FACT THE
 EXACT SAME ENERGY CALCULATIONS WERE RESUBMITTED. PLEASE
 SEE THE ADDRESS WAS CHANGED BY HAND WRITING THIS ON
 COVER SHEETS. WHEN ADDRESSING THE CODE COMPLIANCE
 NOTES, PLEASE CHANGE ADDRESS.
 THE USE AS STATED IN THE ENERGY CALCULATIONS STILL
 INDICATES "SALES" IN MORE THAN ONE LOCATION.
 PLEASE SEE THE SEAL IS STILL NOT CLEAR AND VISIBLE SO
 THAT ALL INFORMATION ON SEAL IS READABLE. SEE NOTE FOR
 SEALS ON PLANS.
 PLEASE SEE THE CONTROLS ON CALCULATIONS STILL INDICATE
 *MANUAL ON/OFF* WHEN IN FACT THE PLANS CONTAINS THE
 OCCUPANCY SENSOR TYPE DEVICES.
 THE REST OF THE COMMENT IS THE SAME FROM PREVIOUS
 REVIEW.
 FIXTURES, WATTAGE ETC DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE,
 NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF
 LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND
 COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO
 NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A
 NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO
 CORRELATE WITH ACTUAL PLANS AND CALCULATIONS
 SUBMITTED.
 PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE
 SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE
 SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE
 OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT
 VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER
 FS 481.221.
 PLEASE SEE THE CONTROL METHODS ON THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2
 ETC.
  
 6) NOTE:PLEASE SEE THIS NOTE REMAINS THE LEVELS ADDED
 ON PLANS FOR ADA COMPLIANCE DOES NOT MEET THE MINIMUM
 LEVELS FOR ADA. THE FBC LEVELS FOR ADA ARE MORE
 STRINGENT THAN THAT OF NFPA-72 LEVELS.
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.
  
 7) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS
 ATTACHED TO NOTES. THIS IS ONLY GIVEN AS A NOTICE AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved