Date |
Text |
2007-04-18 18:28:10 | |
| ** UNSAT2ND REVIEW** |
| |
| |
| 1) NOTE: PLEASE COORDINATE ADDRESS. PLEASE SEE THE |
| PERMIT APPLICATION STILL CONTAINS THE ADDRESS AND |
| PARCEL CONTROL NUMBER (PCN) FOR 600 N. DIXIE WHEN THE |
| SCOPE OF WORK IS BEING DONE AT 600 SOUTH DIXIE. PLEASE |
| BE SURE TO CHANGE APPLICATION AND OWNER INFORMATION AS |
| THE OWNER FOR 600 S DIXIE IS NOT GRAND TRUST BANK. |
| |
| 2) NOTE: PLEASE SEE THAT ALL RAISED SEALS SHALL BE |
| CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL |
| WHICH IS REQUIRED READABLE.THE INFORMATIONON MOST |
| OF THE SEALS ON SHEETS WILL NOT PROVIDE ALL INFORMATION |
| ON SEAL EVEN WHEN USING A LEAD RUB NOT APPLIED WITH |
| PENCIL. |
| PLEASE BE SURE ALL PLANS SHEETS AND ENERGY CALCULATIONS |
| ARE SEALED WITH READABLE RAISED SEAL. |
| FS 481.221, FAC61G1-16.002,.3 |
| |
| 3) NOTE: PLEASE SEE THE NOTE FROM PREVIOUS REVIEW NEEDS |
| TO BE CLARIFIED FOR THESE LOCATIONS. A HANDWRITTEN |
| RESPONSE MENTIONS THERE IS NO ANESTHETIZING AT THIS |
| LOCATION AND TO SEE NOTE #8, HOWEVER NOTE #8 DOES NOT |
| SEEM TO CONTAIN ANY MENTIONING OF THIS? |
| PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. PLEASE |
| SPECIFY AREAS AND USE IN THESE AREAS. PLEASE SPECIFY |
| ANY USE OF ANESTHETIZING LOCATIONS IF THIS APPLIES TO |
| THIS OFFICE AND USE. |
| NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND |
| GROUNDING AS REQUIRED. |
| |
| 4) NOTE: PLEASE KNOW THAT IN NOTED RESPONSE FROM |
| ARCHITECT WHICH WAS WRITTEN ON THE REVIEW NOTES FROM |
| PREVIOUS REVIEW IT MENTIONS "THIS REVIEWER IS GETTING |
| TOO PICKY", PLEASE KNOW THAT THIS REQUIREMENT WAS |
| ADOPTED INTO THE NEW CODE AND THE TEXT IN THE PREVIOUS |
| NOTE WAS EXTRACTED DIRECTLY FROM THE CODE. PLEASE |
| CONTACT THE CODE PANELIST FOR ANY ROP'S (REQUEST FOR |
| PROPOSALS). |
| THIS IS A MINIMUM REQUIREMENT WHICH IS SET FORTH FROM |
| NFPA AND NOT THIS OFFICE. |
| THIS NOTE WILL REMAIN AS THERE ARE SOME ITEMS ON PLANS |
| WHICH MAY NOT INDICATE CIRCUITING AND ITEMS ON PLANS |
| WHICH HAVE NOT BEEN CLEARED UP AND CLARIFICATION FOR |
| DESIGNER ON WHAT WILL BE REQUIRED FOR PROJECTS REVIEWED |
| IN TEH CITY OF WEST PALM BEACH. |
| |
| (NOTE FROM PREVIOUS REVIEW) PLEASE CORRELATE PANEL |
| SCHEDULE AND COMPLETE PANEL SCHEDULE(S) SO THAT ALL |
| ITEMS ON PANEL SCHEDULE ARE SPECIFIC TO AREAS AND ROOMS |
| IN WHICH THEY FEED. PLEASE SEE COMMENTARY BELOW |
| EXTRACTED FROM THE CODE. *SECTION 408.4 WAS REVISED FOR |
| THE 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR |
| EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD |
| BE LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| |
| 5) NOTE: PLEASE SEE THIS NOTE REMAINS. IN FACT THE |
| EXACT SAME ENERGY CALCULATIONS WERE RESUBMITTED. PLEASE |
| SEE THE ADDRESS WAS CHANGED BY HAND WRITING THIS ON |
| COVER SHEETS. WHEN ADDRESSING THE CODE COMPLIANCE |
| NOTES, PLEASE CHANGE ADDRESS. |
| THE USE AS STATED IN THE ENERGY CALCULATIONS STILL |
| INDICATES "SALES" IN MORE THAN ONE LOCATION. |
| PLEASE SEE THE SEAL IS STILL NOT CLEAR AND VISIBLE SO |
| THAT ALL INFORMATION ON SEAL IS READABLE. SEE NOTE FOR |
| SEALS ON PLANS. |
| PLEASE SEE THE CONTROLS ON CALCULATIONS STILL INDICATE |
| *MANUAL ON/OFF* WHEN IN FACT THE PLANS CONTAINS THE |
| OCCUPANCY SENSOR TYPE DEVICES. |
| THE REST OF THE COMMENT IS THE SAME FROM PREVIOUS |
| REVIEW. |
| FIXTURES, WATTAGE ETC DO NOT CORRELATE WITH PLANS. |
| PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE |
| WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE, |
| NUMBER OF FIXTURES ETC. |
| PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF |
| LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND |
| COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO |
| NOT CORRELATE AT ALL AT THIS TIME. |
| PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A |
| NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO |
| CORRELATE WITH ACTUAL PLANS AND CALCULATIONS |
| SUBMITTED. |
| PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE |
| SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE |
| SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE |
| OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT |
| VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER |
| FS 481.221. |
| PLEASE SEE THE CONTROL METHODS ON THE ENERGY |
| CALCULATIONS DO NOT CORRELATE WITH PLANS. |
| PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2 |
| ETC. |
| |
| 6) NOTE:PLEASE SEE THIS NOTE REMAINS THE LEVELS ADDED |
| ON PLANS FOR ADA COMPLIANCE DOES NOT MEET THE MINIMUM |
| LEVELS FOR ADA. THE FBC LEVELS FOR ADA ARE MORE |
| STRINGENT THAN THAT OF NFPA-72 LEVELS. |
| PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE |
| THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA |
| REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. |
| |
| 7) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS |
| ATTACHED TO NOTES. THIS IS ONLY GIVEN AS A NOTICE AT |
| THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |