Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-10 16:01:14DENIED
 REFERENCE: FBC-2004 W/2006 REV.
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SHT 1 ROOM FINISH SCHEDULE. TOILET ROOMS 1 & 2 WALL
 FINISH INDICATES GWB PAINTED. THIS DOES NOT MEET THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT" WALLS AS
 REQUIRED IN SECTION 1210.2. PLEASE INDICATE A HARD
 SURFACE FOR THE WALLS AS REQUIRED.
  
 2. SHT 1 INDICATES A FLOOR DRAIN IN THE LAB. THE RISER
 DIAGRAM INDICATES THIS AS A FLOOR SINK. PLEASE
 CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION
 106.1.1. IF THE FLOOR SINK IS FOR INDIRECT WASTE, THEN
 A FLOOR SINK IS REQUIRED. IF SO PLEASE INDICATE WHAT
 WILL DRAIN INTO THE FLOOR SINK. SECTION 106.1.2.
  
 3. SHT 2 DETAILS 4 & 5. SHOW COMPLIANCE FOR THE
 FOLLOWING:
 -WATER CLOSETS:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 -FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 4. SHT 3 WASTE RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. RISER SHOWS 2 FSC'S IN HYG #1, AND THE FUTURE DL
 & FSC IN OFFICE #1 SHALL BE PIPED THE SAME AS IN THE
 OTHER EXAM ROOMS AS THE FLOOR PLAN IS THE SAME FOR ALL
 ROOMS. PLEASE CORRELATE RISER & FLOOR PLAN. SECTION
 106.1.1.
  
 5. SHT 3 WATER RISER DIAGRAM, IDENTYFY FITTINGS AT THE
 TOP OF ALL DROPS AS THEY ARE NOT IDENTIFIED ON THE
 SYMBOL LEGEND ON SHT 1. SECTION 106.1.1.--A WATER
 HAMMER ARRESTOR IS REQUIRED ON THE ICE MAKER IN THE
 LOUNGE AND THE WASHER IN THE STERILE ROOM AS WELL AS
 ANY OTHER FIXTURE WITH A QUICK CLOSING VALVE. SECTION
 604.9. WHA'S SHALL BE INSTALLED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE OFFICE AND SHALL BE INSTALLED A MAXIMUM OF 4' AFF
 FOR SERVICE AND CERTIFICATION. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved