Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2007-03-10 17:34:05DENIED
 REFERENCE: NFPA 99C 2002
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. 1. AIR COMPRESSORS AND VACUUM PUMPS SHALL BE
 INSTALLED IN A DESIGNATED MECHANICAL EQUIPMENT AREA,
 VENTILATED AND WITH REQUIRED UTILITIES (E.G.,
 ELECTRICITY, DRAINS, LIGHTING, ETC.). SUBMIT A DETAIL
 SHOWING THE COMPRESSOR & VACUUM AND ALL OTHER
 REQUIREMENTS AS DESCRIBED. SECTION 5.3.3..3.7.1.
  
 2. SUBMIT A DETAIL FOR THE COMPRESSOR SHOWING
 COMPLIANCE WITH SECTION 5.3.3.5.3 (1) THRU (17). (SEE
 ATTACHED SHEET - FIGURE A.5.3.3.4).
  
 3. SUBMIT A DETAIL FOR THE VACUUM SHOWING COMPLIANCE
 WITH SECTION 5.3.3.6 AND ALL SUBSECTIONS. (SEE ATTACHED
 SHEET - FIGURES A.5.3.3.6(A),A5.3.3.6(B),
 A5.3.3.6(C), OR A5.3.3.6(D).
  
 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE
 SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6.
  
 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER
 LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT 3 SHOWS WSF (FILTER). THE FILTER SHALL COMPLY
 WITH NSF 42. SECTION 611.1. PLEASE SUBMIT MANUF.
 SPECIFICATION SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]