Plan Review Notes For Permit 07020266 |
Permit Number |
07020266 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-13 15:10:56 | -----------------DENIED----------------- | | | | 1. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING | | MAXIMUM ALLOWABLE ELEVATION DIFFERENCE BETWEEN AHU AND | | ROOFTOP CONDENSING UNIT. ALSO, PLEASE SHOW THE | | ELEVATION DIFFERENCE BETWEEN COMPONENTS AS IT WILL | | OCCUR IN THIS CASE. WILL COPPER LINE SIZES BE AFFECTED | | BY THIS CONDITION? FBC,M 304.1. | | | | 2. PG M1: AIR CONDITIONING CONTROL SEQUENCE | | NOTE #3 - DUCT SMOKE DETECTORS SHALL BE CONNECTED TO | | THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1. | | | | 3. PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL, | | DEMONSTRATING COMPLIANCE WITH FBC,M 307.2. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|