2007-03-13 15:10:56-----------------DENIED-----------------
  
 1. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING
 MAXIMUM ALLOWABLE ELEVATION DIFFERENCE BETWEEN AHU AND
 ROOFTOP CONDENSING UNIT. ALSO, PLEASE SHOW THE
 ELEVATION DIFFERENCE BETWEEN COMPONENTS AS IT WILL
 OCCUR IN THIS CASE. WILL COPPER LINE SIZES BE AFFECTED
 BY THIS CONDITION? FBC,M 304.1.
  
 2. PG M1: AIR CONDITIONING CONTROL SEQUENCE
 NOTE #3 - DUCT SMOKE DETECTORS SHALL BE CONNECTED TO
 THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 3. PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL,
 DEMONSTRATING COMPLIANCE WITH FBC,M 307.2.
  