Plan Review Notes
Plan Review Notes For Permit 07020266
Permit Number 07020266
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-01 07:05:18** UNSAT **
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE:PLEASE CLARIFY WHAT IS BEING SHOWN ON RISER
 OF TWO METERS AND MAINS FOR THIS SINGLE TENANT. PLEASE
 KNOW AS THIS IS ONE OCCUPANCY AND ONE TENANT, ONE METER
 AND MAIN SHOULD BE SHOWN, HOWEVER IT APPEARS TWO ARE
 BEING SHOWN AT THIS TIME??
 PLEASE CLARIFY FBC 106.1.2, 106.3.5.1.2
 104.6.
 PLEASE SEE THIS WOULD ALSO CREATE ZONING AND POSSIBLE
 BUILDING ISSUES WITH ONE OCCUPANCY STATED. ONLY ONE
 TENANT METER WILL BE PERMITTED BASED ON THE SINGLE
 OCCUPANCY AT THIS TIME.
  
 3) NOTE: PLEASE 517.60, 517.62 AND OTHER PARTS OF 517.
 PLEASE SPECIFY AREAS AND USE IN THESE AREAS. PLEASE
 SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF THIS
 APPLIES TO THIS OFFICE AND USE.
 NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND
 GROUNDING AS REQUIRED.
  
 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE
 PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE
 ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED.
 PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 5) NOTE: PLEASE SHOW LOAD CALCULATIONS ON THE EXISTING
 SERVICE (800 AMP DISCONNECT) NEC 220
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42 PLEASE INDICATE THE SIZE OF WHAT IS
 BEING SHOWN FOR THE EXISTING PANEL AND LOAD ON PANEL
 ALONG WITH NEW LOADS.
  
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING,
 WATTAGE, NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF
 LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND
 COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO
 NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A
 NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO
 CORRELATE WITH ACTUAL PLANS AND CALCULATIONS
 SUBMITTED.
 PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE
 SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE
 SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE
 OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT
 VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER
 FS 481.221.
 PLEASE SEE THE CONTROL METHODS ON THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2
 ETC.
  
 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.
  
 8) NOTE: PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS
 WITHOUT DESIGNATIONS, PLEASE INCLUDE FOR REVIEW OF
 CHAPTER 13 REQUIREMENTS.
 PLEASE ALSO SEE 13-415.1.ABC.3 WHERE APPLICABLE.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved