Date |
Text |
2007-03-01 07:05:18 | ** UNSAT ** |
| |
| |
| 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| 8TH, 2006. |
| 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| SUBMITTED |
| 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE |
| STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED |
| IN THIS REVIEWER(S) COMMENTS. |
| |
| 2) NOTE:PLEASE CLARIFY WHAT IS BEING SHOWN ON RISER |
| OF TWO METERS AND MAINS FOR THIS SINGLE TENANT. PLEASE |
| KNOW AS THIS IS ONE OCCUPANCY AND ONE TENANT, ONE METER |
| AND MAIN SHOULD BE SHOWN, HOWEVER IT APPEARS TWO ARE |
| BEING SHOWN AT THIS TIME?? |
| PLEASE CLARIFY FBC 106.1.2, 106.3.5.1.2 |
| 104.6. |
| PLEASE SEE THIS WOULD ALSO CREATE ZONING AND POSSIBLE |
| BUILDING ISSUES WITH ONE OCCUPANCY STATED. ONLY ONE |
| TENANT METER WILL BE PERMITTED BASED ON THE SINGLE |
| OCCUPANCY AT THIS TIME. |
| |
| 3) NOTE: PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. |
| PLEASE SPECIFY AREAS AND USE IN THESE AREAS. PLEASE |
| SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF THIS |
| APPLIES TO THIS OFFICE AND USE. |
| NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND |
| GROUNDING AS REQUIRED. |
| |
| 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE |
| PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE |
| ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. |
| PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION. |
| |
| 5) NOTE: PLEASE SHOW LOAD CALCULATIONS ON THE EXISTING |
| SERVICE (800 AMP DISCONNECT) NEC 220 |
| PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| 215.3, AND 230.42 PLEASE INDICATE THE SIZE OF WHAT IS |
| BEING SHOWN FOR THE EXISTING PANEL AND LOAD ON PANEL |
| ALONG WITH NEW LOADS. |
| |
| |
| 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING, |
| WATTAGE, NUMBER OF FIXTURES ETC. |
| PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF |
| LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND |
| COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO |
| NOT CORRELATE AT ALL AT THIS TIME. |
| PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A |
| NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO |
| CORRELATE WITH ACTUAL PLANS AND CALCULATIONS |
| SUBMITTED. |
| PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE |
| SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE |
| SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE |
| OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT |
| VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER |
| FS 481.221. |
| PLEASE SEE THE CONTROL METHODS ON THE ENERGY |
| CALCULATIONS DO NOT CORRELATE WITH PLANS. |
| PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2 |
| ETC. |
| |
| 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. |
| |
| 8) NOTE: PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS |
| WITHOUT DESIGNATIONS, PLEASE INCLUDE FOR REVIEW OF |
| CHAPTER 13 REQUIREMENTS. |
| PLEASE ALSO SEE 13-415.1.ABC.3 WHERE APPLICABLE. |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |