2007-04-04 09:30:47*** DENIED ***
 **AS NOTED IN LAST REVIEW 2-16-07**
  
 1) MECHANICAL PLANS THAT WERE SUBMITTED HAVE FADED
 INFORMATION (SEE ADDRESS AND EQUIPMENT LISTING) ON THEM
 AND SHOW THE SUPPLY AND RETURN AIR GRILLS AS STRAIGHT
 LINES, A STRAIGHT LINE IS NOT AN ACCEPTABLE SYMBOL FOR
 AN A/C GRILL. SEE 2004 FBC 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ).
  
 2) ALL RECORDS ARE ELECTRONICALLY SCANNED FOR RETENTION
 AND THE PLANS THAT WERE SUBMITTED ARE NOT ACCEPTABLE
 FOR RETENTION, SEE 2004 FBC CITY WPB AMEND. 106.1.3.
  
 3) SEE YELLOW HIGH LIGHTS ON PLANS FOR MISSING
 INFORMATION AND FADED INFORMATION.
  
 4) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.