Plan Review Notes For Permit 07020234 |
Permit Number |
07020234 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-04-04 09:30:47 | *** DENIED *** | | **AS NOTED IN LAST REVIEW 2-16-07** | | | | 1) MECHANICAL PLANS THAT WERE SUBMITTED HAVE FADED | | INFORMATION (SEE ADDRESS AND EQUIPMENT LISTING) ON THEM | | AND SHOW THE SUPPLY AND RETURN AIR GRILLS AS STRAIGHT | | LINES, A STRAIGHT LINE IS NOT AN ACCEPTABLE SYMBOL FOR | | AN A/C GRILL. SEE 2004 FBC 106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE | | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ). | | | | 2) ALL RECORDS ARE ELECTRONICALLY SCANNED FOR RETENTION | | AND THE PLANS THAT WERE SUBMITTED ARE NOT ACCEPTABLE | | FOR RETENTION, SEE 2004 FBC CITY WPB AMEND. 106.1.3. | | | | 3) SEE YELLOW HIGH LIGHTS ON PLANS FOR MISSING | | INFORMATION AND FADED INFORMATION. | | | | 4) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | TIMES THE FEE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|