Plan Review Notes For Permit 07020212 |
Permit Number |
07020212 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-22 07:10:27 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | PROVIDE ROUTING,JUNCION BOX (IF USED) CONDUCTOR AND | | CONDUIT TYPES FOR THE RELOCATED SIGN. | | | | 600.5 BRANCH CIRCUITS. | | (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING | | AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS | | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN | | ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT | | SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE | | OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED | | AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. | | SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED | | ACCESSIBLE TO PEDESTRIANS. | | | | 600.6 DISCONNECTS. | | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUTLINE | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS. SEE 600.6(A)(1) FOR LOCATIION. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPARTMENT | | 561) 805-6718 |
|