2007-02-22 14:42:05 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 I COULD NOT DETERMINE WHICH ARTICLE THE LOAD
 CALCULATION WAS BASED ON. I CALCULATED THE LOAD , USING
 THE INFORMATION GIVEN AND ARRIVED AT 317 AMPS TOTAL,
 USING TABLE 220.84. IF THE DESIGNER DISAGREES WITH THIS
 CALCULATION, PLEASE INDICATE THE ARTICLES BEING USED TO
 ARRIVE AT 243.6 AMPS.
  
 1} THE MINIMUM SIZE FOR THE SERVICE ENTRANCE CONDUCTORS
 IS 400 MCM FOR A 400 AMP SERVICE. 310.15(B)(6), OR 350
 MCM FOR 350AMPS, DEPENDING ON THE LOAD CALCULATION.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED, THE
 GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH 250.66
 AND 250.52, PLEASE INDICATE COMPLIANCE ON THE RISER
 DIAGRAM.
  
 4} THE HOUSE PANEL WAS NOT INCLUDED IN THE
 CALCULATIONS, SEE 220.84(B).
  
 5} PROVIDE A FLOOR PLAN LOCATING THE SERVICE EQUIPMENT
 SO THAT COMPLIANCE WITH 230.70(A)(1) CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  