Plan Review Notes
Plan Review Notes For Permit 07020129
Permit Number 07020129
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-01 11:31:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS
 REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE
 SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN.
 ****NO RESPONSE/NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN ON THE FLOOR PLAN FOR THE FIXTURES.
  
 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE
 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR
 FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE
 WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION
 11-4.17.3 EXCEPTIONS (1)(2).
 ****NO RESPONSE/NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE LAV SHALL BE MINIMUM 15"
 OFF THE WALL TO THE CENTER OF THE FIXTURE TO BE
 CENTERED ON THE 30" WIDTH OF THE CLEAR FLOOR SPACE.
 (RECOMMEND CHANGE THE LAYOUT OF THE ACCESSIBLE STALL IN
 THE WOMEN'S TOILET ROOM. THE LAV CAN BE BEHIND THE W/C
 OF THE MEN'S TOILET ROOM AND COMPLY).
  
 9. OK
  
 ***********NEW COMMENTS***********
  
 1B. SUBMIT A DETAIL FOR THE W/C'S SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ******NO RESPONSE, NOT ADDRESSED
  
 2B. SUBMIT A DETAIL FOR THE STALLS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW
 CONSTRUCTION) (FIG 30E)
 ******RESPONSE NOTED, BUT THE LAV IS NOT SHOWN AS 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE AS
 REQUIRED TO BE CENTERED ON THE FIXTURE.
  
 3B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5(1) CLEARANCES
 D. 11-4.15.5(2) CLEAR FLOOR SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ******NO RESPONSE, NOT ADDRESSED.
  
 4B. SUBMIT A DETAIL FOR THE LAVS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 ******NO RESPONSE, NOT ADDRESSED.
  
 5B. OK
  
 6B. SUBMIT A DETAIL FOR THE SINK SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. -CABINET DOORS
 ARE NOT ALLOWED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 ******RESPONSE NOTED, NOT ADDRESSED.
  
 7B. OK
  
 *****NEW COMMENTS (3RD REVIEW)*****
  
 1C. THE SANITARY AND WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. (SEE EXAMPLE OF A SANT RISER
 DIAGRAM THAT REFLECT THE FLOOR PLAN). PLEASE SUBMIT
 SANT AND WATER RISERS THAT REFLECT THE FLOOR PLAN AFTER
 THE LAV CHANGE IN THE ACCESSIBLE STALL IN THE WOMENS
 TOILET ROOM. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE/NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved