2007-11-11 15:02:28 | REVIEW #: 3RD |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. FLOOR PLAN CALLS FOR A TOTAL OF 930 CFM. A FOUR TON |
| AHU WILL PRODUCE 1600 CFM. WHERE WILL THE OTHER 670 CFM |
| GO? AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED AND |
| INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN |
| ACCORDANCE WITH FBC,M 603.1. |
| |
| 2. THIS COMMENT WAS NOT ADDRESSED. NO OUTSIDE AIR |
| CALCULATIONS PROVIDED. NO OUTSIDE AIR VENTILATION SHOWN |
| ON PLANS. SHOW COMPLIANCE WITH FBC,M 403.3. |
| |
| 3. THIS COMMENT WAS PARTIALLY ADDRESSED. CFM OF BATH |
| EXHAUST FANS STILL NOT SHOWN ON PLANS. SHOW COMPLIANCE |
| WITH FBC,M 403.3. |
| |
| 4. THIS COMMENT WAS NOT ADDRESSED. SHOW COMPLIANCE WITH |
| FBC,M 602.2.1 |
| |
| 5. THIS COMMENT WAS NOT ADEQUATELY ADDRESSED. LOCATION |
| OF CONDENSATE DISPOSAL NOT SHOWN. A SHUTOFF SWITCH ON A |
| CONDENSATE PUMP IS NOT A CODE COMPLIANT MEANS OF |
| AUXILIARY DRAIN PROTECTION. COMPLY WITH ONE OF THE |
| ALLOWED METHODS AS LISTED IN FBC,M SECTION 307.2.3. |
| |
| 6. OK |
| |
| 7. NOW ENERGY CALCULATIONS SHOW 4.8 TONS OF AIR AND |
| MANUAL N SHOWS 5 TONS OF AIR, BUT EQUIPMENT LISTED IS |
| ONLY 4 TONS. PLEASE COORDINATE ALL DOCUMENTATION AND |
| EQUIPMENT LISTING. |
| |
| 8. OK |
| |