2007-11-11 15:02:28REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. FLOOR PLAN CALLS FOR A TOTAL OF 930 CFM. A FOUR TON
 AHU WILL PRODUCE 1600 CFM. WHERE WILL THE OTHER 670 CFM
 GO? AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED AND
 INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN
 ACCORDANCE WITH FBC,M 603.1.
  
 2. THIS COMMENT WAS NOT ADDRESSED. NO OUTSIDE AIR
 CALCULATIONS PROVIDED. NO OUTSIDE AIR VENTILATION SHOWN
 ON PLANS. SHOW COMPLIANCE WITH FBC,M 403.3.
  
 3. THIS COMMENT WAS PARTIALLY ADDRESSED. CFM OF BATH
 EXHAUST FANS STILL NOT SHOWN ON PLANS. SHOW COMPLIANCE
 WITH FBC,M 403.3.
  
 4. THIS COMMENT WAS NOT ADDRESSED. SHOW COMPLIANCE WITH
 FBC,M 602.2.1
  
 5. THIS COMMENT WAS NOT ADEQUATELY ADDRESSED. LOCATION
 OF CONDENSATE DISPOSAL NOT SHOWN. A SHUTOFF SWITCH ON A
 CONDENSATE PUMP IS NOT A CODE COMPLIANT MEANS OF
 AUXILIARY DRAIN PROTECTION. COMPLY WITH ONE OF THE
 ALLOWED METHODS AS LISTED IN FBC,M SECTION 307.2.3.
  
 6. OK
  
 7. NOW ENERGY CALCULATIONS SHOW 4.8 TONS OF AIR AND
 MANUAL N SHOWS 5 TONS OF AIR, BUT EQUIPMENT LISTED IS
 ONLY 4 TONS. PLEASE COORDINATE ALL DOCUMENTATION AND
 EQUIPMENT LISTING.
  
 8. OK
  