Plan Review Notes
Plan Review Notes For Permit 07020129
Permit Number 07020129
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-17 11:55:202007-10-17 11:55:20
  
 *** DENIED 3RD REVIEW *****
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS STILL NEED
 TO BE ADDRESSED ALONG WITH NEW COMMENTS AS PLANS/RISER
 HAS BEEN REVISED ONCE AGAIN.
  
  
 1) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS.
 PLEASE STATE AND SHOW ON PLANS THE RELEVANT CODE IN
 WHICH PROJECT IS DESIGNED UNDER.
 THE YEARS FOR CODES ARE REQUIRED.
 PLEASE ALSO SEE PALM BEACH COUNTY IS BEING NOTED ON
 SHEET E-1 WHEN PROJECT IS IN THE CITY OF WEST PALM
 BEACH.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 INDICATE CODES NEEDED.
  
 2) NOTE:PLEASE CORRELATE ELECTRICAL ON PLANS WITH
 THAT OF THE ARCHITECTURAL AND MECHANICAL PLANS. FOR
 EXAMPLE: PLEASE SEE THE LOCATION OF THE NEW SUB PANEL
 ON A AND M SHEETS ARE IN A COMPLETELY SEPARATE LOCATION
 AND THE SIZE OF THE PANEL IS NOT THE SAME AS THE
 ELECTRICAL PLANS.
 PLEASE LABEL ALL ELECTRICAL EQUIPMENT ON PLANS FOR
 ELECTRICAL. * PANEL *A*, ETC.
 NEC 110.26, 240.4, 215.5, 230,ETC
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AS
 SUBMITTED ALONG WITH LOAD CALCULATIONS AND PLANS DO NOT
 CORRELATE WITH NUMEROUS ITEMS. THIS REVIEWER CAN ONLY
 GIVE A FEW EXAMPLES AS THERE ARE TOO MANY ITEMS WHICH
 DO NO MATCH AND DO NOT THE MINIMUM REQUIREMENTS OF THE
 ELECTRICAL CODE.
  
 FOR EXAMPLE:
 PLEASE SEE E-1 ABOVE ELECTRICAL LEGEND WHICH INDICATES
 A 400AMP MLO PANEL, YET THERE IS NO WHERE ON ELECTRICAL
 RISER WHICH INDICATES A 400MLO PANEL.
 PLEASE SEE LOAD CALCULATIONS WHICH INDICATE PANEL *C*
 AND *LP* AS EXISTING CHURCH AND NEW FELLOWSHIP HALL,
 YET THE PANEL SCHEDULES TO THE RIGHT DO NOT INDICATE
 THE SAME LOADS OR PANEL SIZES.
 PLEASE SEE RISER WHICH SHOWS PANEL *C* AS 125AMP, YET
 PANEL SCHEDULES SHOW BOTH *C* AND *LP* AS 200AMP. HOW
 CAN *C* AND *LP* PANEL SCHEDULE BE THE SAME WHEN THEY
 CLEARLY DO NOT HAVE THE SAME CIRCUITS?
 PLEASE SEE RISER SHOWS 3PHASE EQUIPMENT, PANELS SERVICE
 ETC INCLUDING AS NOTED FOR CONDUCTOR COLOR CODING YET
 THE RISER AND SEVERAL OTHER LOCATIONS ONLY INDICATE A
 SINGLE PHASE SERVICE.
  
 **THE ABOVE ARE ONLY SOME OF THE INCONSISTENCIES ON
 PLANS. THERE ARE SEVERAL OTHER ITEMS WHICH ARE TOO MANY
 TO LIST.
 ** PLEASE SUBMIT ELECTRICAL PLANS, LOAD CALCULATIONS,
 AND RISER DIAGRAM WHICH CORRELATE, ARE CODE COMPLIANT
 AND CAN BE REVIEWED AS AN ELECTRICAL INSTALLATION. MAY
 NOT HAVE A 40 SPACE MLO AS DISTRIBUTION PANEL. NEC,
 100, 230.70,71,72,76,79, 215.5, 310.16, 240.4 ETC
 **2005 NATIONAL ELECTRICAL CODE**
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE 700.12F AS ALL EXIT AND EMERGENCY
 LIGHTING FIXTURES AS NOTED ON THE PREVIOUS REVIEWS ARE
 REQUIRED TO BE CIRCUITED TO THE NORMAL BRANCH CIRCUIT
 LIGHTING IN THAT AREA. PLEASE SEE THAT PLANS HAVE
 REVISED AND CORRECTED MOST OF THESE BUT NOT ALL. (END
 OF FELLOWSHIP HALL)
  
 5) NOTE:PLEASE KNOW THAT COMPLETE LOAD CALCULATIONS
 WHICH MEET THE MINIMUM REQUIRED BY CODE. THE SAME
 SECTIONS AS GIVEN IN THE PREVIOUS TWO REVIEWS REMAIN.
 THE CALCULATIONS ARE STILL SHOWING ONE CALCULATION FOR
 NEW PANELS WHICH ARE NOT THE SAME AS PANEL SCHEDULES OR
 PLANS. THIS WAS NOTED ABOVE FOR COORDINATION OF PLAN
 HOWEVER AS THIS WAS SPECIFICALLY NOTED ON PREVIOUS
 REVIEW, IT IS BEING NOTED ONCE AGAIN.
 PLEASE SUBMIT LOAD CALCULATIONS WHICH ARE CODE
 COMPLAINT, CORRELATE WITH PLANS, AND PANEL SCHEDULES.
 FOR EXAMPLE, PLEASE SEE SEVERAL BRANCH CIRCUITS WHICH
 ARE SHOWING LOADS WHICH EXCEED THE RATINGS FOR THE
 BRANCH CIRCUIT. SEE ONE SET OF PLANS ARE REDLINED FOR
 SOME OF THESE CIRCUITS SUCH AS CIRCUIT #15 ON *C*/LP*,
 WHICH SHOWS 3.6KW ON A SINGLE POLE 20AMP CIRCUIT.
 (3600VA DIVIDED BY 120V IS 30AMPS) THIS IS NOT
 PERMITTED ON THE BRANCH CIRCUIT. (TYPICAL MAXIMUM LOAD
 ON A 20AMP BRANCH CIRCUIT IS 1920VA).
 SEE CIRCUITS #6, #15, #24 ETC ON LP-A, #8, #15, #16,
 #17, #18 ETC ON *C* *LP*.
 PLEASE SEE NEC 220, 220.12, 220.14, 220.42, 220.44,
 ETC.
 215.5, 215.3, 230.42 ETC
 310.16, 240.4 ETC.
 210.3, 210.20, 210.23 ETC.
 PLEASE KNOW THERE ARE SEVERAL AND TOO MANY SPECIFIC
 CODE SECTIONS TO STATE ON REVIEW NOTES. PLEASE SEE NEC
 2005.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE AS PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR PANEL *C*/*LP* SHOWS A PANEL AS
 200AMPS AND LOADS WHICH EXCEEDS THE 125AMP RATING OF
 PANEL ON RISER (AS SHOWN) PLEASE BE SURE TO SEE 250.122
 FOR SIZING ADJUSTMENTS OF THE EQUIPMENT GROUNDING
 CONDUCTOR. PLEASE KNOW IN ANY CASE THE #8 AS SHOWN ON
 RISER FOR THE 125AMP PANEL IS TOO SMALL PER 250.122 **
 THIS WILL BE REQUIRED TO BE COORDINATED WITH THE NOTED
 ABOVE WITH RESPECT TO RISER ETC.
  
 7) NOTE: PLEASE VERIFY 250MCM FROM MAIN DISCONNECT TO
 PANEL *LP* ON RISER.. THIS IS BEING SHOWN AS A 200AMP
 PANEL. PLEASE VERIFY THAT THE LUGS ON THIS EQUIPMENT
 WILL ACCEPT THE 250MCM.
 110.3, 90.7, 110.14 FOR LISTING OF EQUIPMENT.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR TO PANEL *LP*>
 250.110, 250.24, 250.122
  
 9) NOTE: PLEASE SUBMIT THE PANEL DESIGNATIONS AND PANEL
 SCHEDULES FOR EACH OF THE PANELS WHICH ARE SHOWN ON
 RISER. AS NOTED ABOVE IN NOTES #5 AND #2, THERE IS
 COORDINATION NEEDED.
 PLEASE SEE ONLY TWO PANEL SCHEDULES WERE SUBMITTED AND
 REVIEW FOR CODE COMPLIANCE COULD NOT BE COMPLETED.
 408.4, 215.5,240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE SEE NEW NOTE ADDED TO THE LOWER LEFT
 HAND SIDE OF E-2 WHICH STATES *PREVIOUS PERMIT
 #07020129 EXPIRED*. HOW IS THIS POSSIBLE WHEN THIS
 PERMIT WHICH IS CURRENTLY IN REVIEW IS STILL THE SAME
 PERMIT WHICH HAS NOT EXPIRED?
 PLEASE ADJUST PLANS.
 ** THE PREVIOUS PERMIT APPLICATION DID EXPIRE HOWEVER
 WAS NEVER ISSUED FOR PERMIT. THAT PERMIT NUMBER IS
 05010378.
 THIS DOES NOT NEED TO BE ON PLANS AS IT WAS NEVER
 ISSUED AND WORK WAS NOT DONE UNDER THAT PERMIT.
  
 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 HAS
 NOT YET BEEN ACHIEVED.
 A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO
 NOT CORRELATE WITH PLANS. PLEASE BE SURE TO SEE
 MECHANICAL REVIEW FOR POSSIBLE METHOD OF CALCULATION
 COMMENT.
 PLEASE SEE THERE SEEMS TO BE TWO DIFFERENT TYPES OF
 LIGHTING FIXTURES ON PLANS AS E-1 SHOWS A COMPLETELY
 DIFFERENT TYPE OF LIGHT FIXTURE/SYMBOL THAN ON E-2.
 PLEASE SEE THE FIXTURE LEGEND DOES NOT CONTAIN THE
 COMPLETE WATTAGE INFORMATION FOR ALL LIGHT FIXTURES
 (EXAMPLE RECESSED FLUORESCENT LIGHT). PLEASE BE SURE
 THIS INFORMATION CORRELATES WITH THE INPUT DATA
 REPORT.
 PLEASE SEE THE EXTERIOR LIGHTS ON THE PLANS DO NOT
 CORRELATE WITH THE INPUT DATA REPORT OR THE FIXTURE
 LEGEND. ONE ITEM FOR EXAMPLE IS THAT THE WALL PACK
 FIXTURE WHICH IS ON LEGEND BUT *BLANK*?
 PLEASE SEE THE INPUT DATA REPORT SHOWS TWO TYPES OF
 FIXTURES, YET NEITHER OF THESE IS ON FIXTURE LEGEND.
 PLANS DO SHOW THREE TYPES OF LIGHTING FIXTURES
 OUTSIDE.
 PLEASE COMPLETE FIXTURE TYPE DESIGNATIONS ON PLANS AND
 FIXTURE LEGEND SO THESE CORRELATE. THEN PLEASE
 CORRELATE ALL LIGHTING INFORMATION ON PLANS WITH THAT
 OF THE INPUT DATA REPORT.
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A, .B, .C, 13-415.2,
 13-415.2.ABC.1.3 ETC.
 ** PLEASE SEE ONLY ONE COPY OF THE INPUT DATA REPORT
 WAS SUBMITTED. PLEASE SUBMIT TWO COPIES AS ONE WILL BE
 STAMPED FOR FILE AND THE OTHER IS STAMPED FOR FIELD SET
 OF PLANS.
 B) PLEASE SEE THE PLANS DO NOT INDICATE ANY METHOD OF
 CONTROLS FOR EXTERIOR LIGHTING WHICH COMPLIES WITH
 13-415.1.ABC.1, 13-415.1.ABC.1.4
 PLEASE SEE NO CONTROLS ARE SHOWN FOR 13-415.1.ABC.1,
 13-415.1.ABC.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. PLEASE SEE THERE ARE SEVERAL CODE SECTIONS
 WHICH WERE REPEATED AND THE FEE HAS BEEN ASSESSED AS
 REQUIRED BY THE FLORIDA STATUTES.
 THIS FEE IS DUE BEFORE PLANS CAN BE RE-SUBMITTED FOR
 THE NEXT REVIEW. THIS FEE IS NOT THE RESPONSIBILITY OF
 THE CONTRACTOR OR OWNER. THIS IS SET-FORTH BY THE
 BOARDS AND THE STATE FOR THE DESIGN PROFESSIONAL. THE
 FEE IS $1860.00
 ** PLEASE KNOW ONE COPY OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS WILL BE RETAINED BY THIS OFFICE. OTHER
 SHEETS MAY BE RETAINED BY OTHER TRADES.
  
 13) NOTE: PLEASE SEE ONCE AGAIN THE ARCHITECT ON
 ELECTRICAL PLANS DID NOT DATE THE PLANS WHEN THEY WERE
 SIGNED AND SEALED. THIS WAS A NOTE GIVEN ON PREVIOUS
 REVIEWS AND IS STILL REQUIRED AS THIS IS A FLORIDA
 STATUTE.
 PLEASE SEE 481.221
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-16 15:53:172007-10-17 15:53:17
  
 PLANS REMOVED FROM INCOMING FOR REVIEW DUE TO DATE FOR
 WHICH ELECTRICAL REVIEWER IS UP TO.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR
 COMMERCIAL BOARD ONCE REVIEW IS COMPLETED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved