2007-07-14 07:47:52 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW**** |
| |
| 1. OK |
| |
| 2. SHOW THE SQUARE FOOTAGE OF THE BUILDING ON THE |
| PLANS. SECTION 106.1.2. |
| ****NO RESPONSE/NOT ADDRESSED |
| |
| 3. OK |
| 4. OK |
| |
| 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES. AS SHOWN |
| THERE APPROXIMATELY 1,158SSF NET DIVIDED BY 5 NET AS |
| INDICATED IN TABLE 1004.1.2 THERE ARE 232 OCCUPANTS. |
| PER TABLE 403.1 232 DIVIDED BY 2 EQUALS 116 MEN - 116 |
| WOMEN. DIVIDED BY 40 EQUALS 2.9 OR 3 WATER CLOSETS EACH |
| REQUIRED FOR MEN AND WOMEN, WITH 2 LAVS EACH FOR MEN |
| AND WOMEN. |
| ****NO RESPONSE/NOT ADDRESSED |
| |
| 6. OK |
| |
| 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS |
| REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30" |
| WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE |
| SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE |
| DRINKING FOUNTAIN. |
| ****NO RESPONSE/NOT ADDRESSED |
| |
| 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE |
| 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR |
| FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE |
| WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION |
| 11-4.17.3 EXCEPTIONS (1)(2). |
| ****NO RESPONSE/NOT ADDRESSED |
| |
| 9. OK |
| |
| ***********NEW COMMENTS*********** |
| |
| 1B. SUBMIT A DETAIL FOR THE W/C'S SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.4 GRAB BARS |
| D. 11-4.16.5 FLUSH CONTROLS |
| E. 11-4.16.6 DISPENSERS |
| |
| 2B. SUBMIT A DETAIL FOR THE STALLS SHOWING COMPLIANCE |
| WITH THE FOLLOWING: |
| A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW |
| CONSTRUCTION) (FIG 30E) |
| |
| 3B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| COMPLIANCE WITH THE FOLLOWING: |
| A. 11-4.15.2 SPOUT HEIGHT |
| B. 11-4.15.3 SPOUT LOCATION |
| C. 11-4.15.5(1) CLEARANCES |
| D. 11-4.15.5(2) CLEAR FLOOR SPACE |
| E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| |
| 4B. SUBMIT A DETAIL FOR THE LAVS SHOWING COMPLIANCE |
| WITH THE FOLLOWING: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| E. 11-4.19.6 MIRRORS |
| |
| 5B. PER SECTION 11-4.22.3 SHOW A 5' TURNING AREA IN THE |
| TOILET ROOMS. |
| |
| 6B. SUBMIT A DETAIL FOR THE SINK SHOWING COMPLIANCE |
| WITH THE FOLLOWING: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH |
| REQUIRED MAX 19" UNDERNEATH THE SINK. -CABINET DOORS |
| ARE NOT ALLOWED. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS |
| |
| 7B. SUBMIT A PLUMBING FLOOR PLAN INDICATING THE |
| CONNECTIONS FOR THE SANITARY BUILDING DRAIN AND THE |
| WATER SERVICE FOR THE ADDITION. SECTION 106.1.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| ****NO RESPONSE/NOT ADDRESSED |
| |