Plan Review Notes
Plan Review Notes For Permit 07020129
Permit Number 07020129
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-14 07:47:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
  
 1. OK
  
 2. SHOW THE SQUARE FOOTAGE OF THE BUILDING ON THE
 PLANS. SECTION 106.1.2.
 ****NO RESPONSE/NOT ADDRESSED
  
 3. OK
 4. OK
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES. AS SHOWN
 THERE APPROXIMATELY 1,158SSF NET DIVIDED BY 5 NET AS
 INDICATED IN TABLE 1004.1.2 THERE ARE 232 OCCUPANTS.
 PER TABLE 403.1 232 DIVIDED BY 2 EQUALS 116 MEN - 116
 WOMEN. DIVIDED BY 40 EQUALS 2.9 OR 3 WATER CLOSETS EACH
 REQUIRED FOR MEN AND WOMEN, WITH 2 LAVS EACH FOR MEN
 AND WOMEN.
 ****NO RESPONSE/NOT ADDRESSED
  
 6. OK
  
 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS
 REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE
 SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN.
 ****NO RESPONSE/NOT ADDRESSED
  
 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE
 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR
 FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE
 WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION
 11-4.17.3 EXCEPTIONS (1)(2).
 ****NO RESPONSE/NOT ADDRESSED
  
 9. OK
  
 ***********NEW COMMENTS***********
  
 1B. SUBMIT A DETAIL FOR THE W/C'S SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 2B. SUBMIT A DETAIL FOR THE STALLS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW
 CONSTRUCTION) (FIG 30E)
  
 3B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5(1) CLEARANCES
 D. 11-4.15.5(2) CLEAR FLOOR SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 4B. SUBMIT A DETAIL FOR THE LAVS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 5B. PER SECTION 11-4.22.3 SHOW A 5' TURNING AREA IN THE
 TOILET ROOMS.
  
 6B. SUBMIT A DETAIL FOR THE SINK SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. -CABINET DOORS
 ARE NOT ALLOWED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 7B. SUBMIT A PLUMBING FLOOR PLAN INDICATING THE
 CONNECTIONS FOR THE SANITARY BUILDING DRAIN AND THE
 WATER SERVICE FOR THE ADDITION. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE/NOT ADDRESSED
  