2007-06-29 15:08:34 | -----------------DENIED----------------- |
| FBC 2004 CODE FAMILY W/ 2006 REVISIONS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PLEASE PROVIDE CFMS FOR ALL SUPPLY DROPS, REGISTERS |
| AND GRILLS. FBC 106.1.2 |
| |
| 2. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING SIZE |
| AND LOCATION OF OUTDOOR AIR SOURCE, OCCUPANCY |
| CLASIFICATION, OCCUPANT LOAD AND CFM OF OUTDOOR AIR |
| REQUIRED PER FBC,M 403.3 AND FBC 106.3.5.1.4 |
| |
| 3. PLEASE SHOW CFM, DUCT SIZE AND DISCHARGE LOCATION |
| FOR TOILET ROOM EXHAUST FANS PER FBC,M 401.5, TABLE |
| 403.3 AND FBC 106.3.5.1.4 |
| |
| 4. A/C CLOSET LOOKS TO BE USED AS A PLENUM. DRAIN LINE |
| MATERIAL IS SHOWN ON PLAN TO BE 3/4" PVC WHICH MAY NOT |
| BE USED IN A PLENUM PER FBC,M 602.2.1. |
| |
| 5. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE |
| DISPOSAL PER FBC,M 307.2.1 AND MEANS OF SECONDARY OR |
| AUXILIARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO, |
| PLEASE SHOW ROUTING OF REFRIGERANT LINES. ARE THEY |
| OVERHEAD OR UNDERGROUND? FBC,M 1107.2.1 |
| |
| 6. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS |
| INCLUDING SIZE, SEER, MODEL NUMBERS, HEAT STRIP AND |
| ELQUIPMENT ELECTRICAL RATINGS. FBC 106.3.5.1.3 |
| |
| 7. ENERGY CALCULATIONS STATE MAX TONNAGE AT 4, BUT |
| PLANS CALL FOR 5 TONS OF COOLING. PLEASE SHOW |
| CORRELATION BETWEEN PLANS AND ENERGY CALCULATIONS. |
| NOTE: MANUAL N, COOLING LOADS AND ENERGY CALCULATIONS |
| MAY NEED TO BE ADJUSTED ONCE ABOVE ADJUSTMENTS ARE |
| MADE. |
| |
| 8. WHAT IS THE PURPOSE OF TWO RETURN GRILLS CONNECTED |
| BY A 14" DUCT IN THE MIDDLE OF A NON-SEPARATED SPACE? |
| WHAT IS THE SIZE OF THE GRILLS? WILL THERE BE SOME SORT |
| OF PARTITION DIVIDING THE SPACE? THERE IS NONE SHOWN ON |
| A/C OR ARCHITECTURAL PLANS. IF THERE IS TO BE A |
| PARTITION, THE RETURN DUCT IS TOO SMALL TO MEET THE |
| BALANCED RETURN EXCEPTIONS OF FBC,M 601.4. THE RETURN |
| DUCT WOULD NEED TO BE AT LEAST 16" TO CLAIM THE |
| EXCEPTION. IF THERE IS TO BE A FOLDING OR ACCORDIAN |
| STYLE PARTITION, PLEASE CHECK FOR STRUCTURAL |
| REQUIREMEMNTS, AS NONE ARE SHOWN ON PLANS AT THIS |
| TIME. |
| |