Plan Review Notes
Plan Review Notes For Permit 07020129
Permit Number 07020129
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-29 15:08:34-----------------DENIED-----------------
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE PROVIDE CFMS FOR ALL SUPPLY DROPS, REGISTERS
 AND GRILLS. FBC 106.1.2
  
 2. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING SIZE
 AND LOCATION OF OUTDOOR AIR SOURCE, OCCUPANCY
 CLASIFICATION, OCCUPANT LOAD AND CFM OF OUTDOOR AIR
 REQUIRED PER FBC,M 403.3 AND FBC 106.3.5.1.4
  
 3. PLEASE SHOW CFM, DUCT SIZE AND DISCHARGE LOCATION
 FOR TOILET ROOM EXHAUST FANS PER FBC,M 401.5, TABLE
 403.3 AND FBC 106.3.5.1.4
  
 4. A/C CLOSET LOOKS TO BE USED AS A PLENUM. DRAIN LINE
 MATERIAL IS SHOWN ON PLAN TO BE 3/4" PVC WHICH MAY NOT
 BE USED IN A PLENUM PER FBC,M 602.2.1.
  
 5. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE
 DISPOSAL PER FBC,M 307.2.1 AND MEANS OF SECONDARY OR
 AUXILIARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO,
 PLEASE SHOW ROUTING OF REFRIGERANT LINES. ARE THEY
 OVERHEAD OR UNDERGROUND? FBC,M 1107.2.1
  
 6. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS
 INCLUDING SIZE, SEER, MODEL NUMBERS, HEAT STRIP AND
 ELQUIPMENT ELECTRICAL RATINGS. FBC 106.3.5.1.3
  
 7. ENERGY CALCULATIONS STATE MAX TONNAGE AT 4, BUT
 PLANS CALL FOR 5 TONS OF COOLING. PLEASE SHOW
 CORRELATION BETWEEN PLANS AND ENERGY CALCULATIONS.
 NOTE: MANUAL N, COOLING LOADS AND ENERGY CALCULATIONS
 MAY NEED TO BE ADJUSTED ONCE ABOVE ADJUSTMENTS ARE
 MADE.
  
 8. WHAT IS THE PURPOSE OF TWO RETURN GRILLS CONNECTED
 BY A 14" DUCT IN THE MIDDLE OF A NON-SEPARATED SPACE?
 WHAT IS THE SIZE OF THE GRILLS? WILL THERE BE SOME SORT
 OF PARTITION DIVIDING THE SPACE? THERE IS NONE SHOWN ON
 A/C OR ARCHITECTURAL PLANS. IF THERE IS TO BE A
 PARTITION, THE RETURN DUCT IS TOO SMALL TO MEET THE
 BALANCED RETURN EXCEPTIONS OF FBC,M 601.4. THE RETURN
 DUCT WOULD NEED TO BE AT LEAST 16" TO CLAIM THE
 EXCEPTION. IF THERE IS TO BE A FOLDING OR ACCORDIAN
 STYLE PARTITION, PLEASE CHECK FOR STRUCTURAL
 REQUIREMEMNTS, AS NONE ARE SHOWN ON PLANS AT THIS
 TIME.
  