Plan Review Notes For Permit 07020129 |
Permit Number |
07020129 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-23 12:35:06 | *****DENIED***** | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW | | STILL NEED TO BE ADDRESSED: | | | | | | 4.INDICATE THE OCCUPANT LOAD FOR THE PROPOSED | | STRUCTURE BASED UPON THE OCCUPANT LOAD FACTORS THAT ARE | | CHARACTERISTIC OF THE USE OF THE SPACE OR DETERMINED AS | | THE MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER | | CONSIDERATION, WHICHEVER IS GREATER. | | | | 5.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA | | HAVING AN OCCUPANT LOAD OF 100 OR MORE SHALL BE | | PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. | | | | 6.PLEASE PROVIDE A LAYOUT SHOWING THE ARRANGEMENT OF | | FURNISHINGS, TABLES, SEATS, AND(OR) EQUIPMENT. | | | | 7.SHOW THE LOCATION OF THE 2A10BC FIRE | | EXTINGUISHER(S). | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|