Plan Review Notes
Plan Review Notes For Permit 07020129
Permit Number 07020129
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-24 12:18:15 
  
 *** UNSAT 2ND REVIEW***
  
 ** PLANS FAILED FOR MANY OF THE SAME ITEMS AS STATED ON
 PREVIOUS REVIEW. PLEASE SEE THERE ARE ALSO NEW COMMENTS
 BASED ON REVISIONS AND CHANGES MADE TO PLANS.
 ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER
 05010378 WHICH BECAME *EXPIRED*.
  
  
 1) NOTE:THIS REMAINS THE SAME NOTE AS THIS
 INFORMATION WAS NOT PLACED ON PLANS.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 INDICATE CODES NEEDED.
  
 2) NOTE:PLEASE CORRELATE ELECTRICAL ON PLANS WITH
 THAT OF THE PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE COMMENTS BELOW WITH RESPECT TO
 CIRCUITING WHICH IS STILL NOT CORRECT.
 NEC 408.4
 PLEASE CORRELATE AND COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
 PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE PANEL
 SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE
 SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE
 SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR
 RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 3) NOTE: PLEASE SEE THIS IS THE SAME NOTE AS PREVIOUS
 REVIEW. PLEASE SEE SEVERAL EMERGENCY LIGHTS AND EXIT
 LIGHTS ARE STILL BEING SHOWN ON DEDICATED CIRCUITS
 WHICH ARE ONLY PERMITTED UNDER CERTAIN CONDITIONS,
 BASED ON PLANS THE EXCEPTIONS AS STATED IN THE NEC DOES
 NOT APPLY AND THESE FIXTURES ARE REQUIRED TO BE
 CIRCUITED TO THE LOCAL LIGHTING CIRCUIT IN ANY ONE
 AREA. PLEASE SEE THE NOTE WITH RESPECT TO LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12F FOR EMERGENCY AND EXIT LIGHTS.
 THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER
 PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO
 PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER
 AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE,
 NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 4) NOTE:PLEASE KNOW THAT COMPLETE LOAD CALCULATIONS
 FOR THE PROPOSED SERVICE AND PANELS AS PREVIOUSLY
 REQUESTED HAS NOT BEEN SUBMITTED.
 PLEASE SEE TWO SEPARATE LOAD CALCULATIONS SHOWN FOR
 SAME PANEL?
 FBC 106.1.2, 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW PER, 220.12,
 220.14, 220.42, 220.44 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL
 CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE
 SUB PANEL *C*.
 PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED
 ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE
 SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL
 SCHEDULE(S). (SIGN CIRCUIT)
  
 5) NOTE: PLEASE SEE ONCE AGAIN THE SERVICE RISER HAS
 BEEN REVISED AND IS STILL NOT CODE COMPLIANT. PLEASE
 SEE NOTES ON E-1 WHICH STATES THIS NEW SERVICE IS A MLO
 PANEL WHEREAS THE RISER INDICATES THIS AS A METER/MAIN
 COMBO? 230.70, 230.71 (MAIN REQUIRED). PLEASE SEE THE
 RISER SHOWS AND NOTES THIS SERVICE AS NEW YET THE RISER
 ALSO CONTAINS NOTES FOR EXISTING? PLEASE SEE THE
 FEEDERS FOR THE NEW 200AMP PANEL ARE NOT CODE COMPLIANT
 PER 310.16
 PLEASE SEE THE RISER WHICH SHOWS TWO MAIN DISCONNECTS:
 ONE 200AMPS AND THE OTHER 150AMPS BOTH FEEDING A SINGLE
 CONDUIT WITH 2/0 FEEDERS TO A GUTTER WHICH TAPS TO
 125AMP PANEL AND A 150AMP PANEL. THIS ENTIRE SCENARIO
 IS NOT CODE COMPLIANT FROM THE FEEDERS, THE TAPS, TO
 TERMINATION IN OPC, THE SINGLE CONDUIT WITH TWO
 BREAKERS SHOWN FEEDING ONE? ETC ETC. PLEASE SEE 215.5,
 310.16, 240.4, 408, 240.21 ETC. THERE ARE TOO MANY CODE
 SECTIONS TO BE REFERENCED.
 PLEASE SUBMIT A CODE COMPLIANT RISER.
 PLEASE SUBMIT THE PANEL SCHEDULES WHICH INDICATE THE
 OCP FEEDING TO SUB PANELS.
 PLEASE SEE THE 2005 NEC AND KNOW IF ANY OF THESE
 CONDITIONS EXIST AT THIS LOCATION AS SHOWN ON PLANS,
 THE ENTIRE ELECTRICAL SERVICE WILL BE REQUIRED TO
 BROUGHT UP TO CODE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS NOW BEEN
 SUBMITTED AND IS MISSING INFORMATION NEEDED FOR CODE
 COMPLIANCE AND FOR REVIEW.
 PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN
 THIS ONE COMMENT.
 A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AND MAINS.
 B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON
 PLANS.
 C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE
 SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE
 FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON
 THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS.
 PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS,
 DIFFERENT OVER CURRENT PROTECTION ETC.
 D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED
 FOR SERVICE.
 ETC.
 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC
 PLEASE SEE 2005 NEC.
  
 6) NOTE:PLEASE SEE COMPLIANCE WITH CHAPTER 13 HAS NOT
 BEEN MET.
 PLEASE SEE NO DESIGN CHANGES OR CONSIDERATION WAS GIVEN
 TO PREVIOUS NOTES WITH RESPECT TO LIGHTING CONTROLS
 REQUIRED.
 PLEASE SEE NO INFORMATION OR RESPONSE TO THESE COMMENT
 TO PROVIDE INFORMATION FOR REVIEW WAS IN PACKAGE SO THE
 COMMENTS REMAIN.
 PLEASE SEE NO TIMED SCHEDULING SYSTEM IS SHOWN IF IN
 DESIGN, OTHER MEANS OF LIGHTING CONTROLS MAY BE SUED.
 PLEASE SEE NO AUTOMATED DEVICES ARE SHOWN.
 PLEASE SEE NO OVER RIDE TIMES ARE SHOWN.
 PLEASE SEE NO DEVICE LOCATIONS WERE SHOWN.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED FOR
 METHOD OF CONTROLS IS NOT CORRECT.
 PLEASE SEE NO OWNER AGENT WAS SIGNED ON SHEETS AS
 REQUIRED.
 PLEASE SEE THE FIXTURE LEGEND IS NOT COMPLETE WITH ALL
 INFORMATION FOR FIXTURES FOR COORDINATION REVIEW WITH
 THE SUBMITTED ENERGY CALCULATIONS.
 PLEASE SEE NOTE WITH RESPECT TO THE ENGINEER AS SHOWN
 CERTIFYING THE ENERGY CALCULATIONS.
 PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN. PLEASE
 SEE NOT RESPONSE LETTER WAS SUBMITTED OR INFORMATION
 FOR THIS.
 PLEASE SEE COMPLIANCE WITH THE 2004 FBC CHAPTER 13 FOR
 CONTROL OF LIGHTING PER 13-415.1ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE13-415.1.AB.1.1, 13-415.2 FOR LIGHTING
 PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS. PLEASE BE SURE TO HAVE THE DESIGNER OF
 RECORD SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS WHICH
 INDICATE LOADS WHICH EXCEED THE RATING OF THE BREAKERS
 AS SHOWN. 240
  
 ** PREVIOUS REVIEW NOTES*
 PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES AND OVER
 CURRENT PROTECTION DEVICES ON PANEL SCHEDULES. PLEASE
 SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,; HOWEVER SEE
 LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE 1-POLE 45AMP
 BREAKERS, SEE #8 AWG ON 20AMP BREAKERS, SEE 30AMP
 BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC ETC. 240.4,
 310.16 ETC.
 SEE 2005 NEC.
  
  
 8) NOTE: PLEASE SEE THE SIGNATURE AS SHOWN ON ENERGY
 CALCULATIONS DOES NOT APPEAR TO BE THE SAME AS THE
 SIGNATURE ON FILE FOR THIS DESIGNER OF RECORD. FS
 471.025/ FAC 61G15-23.002
 PLEASE SUBMIT A SIGNED, DATED, SEALED, AND NOTARIZED
 LETTER FOR LEGAL SIGNATURE VERIFICATION.
 PLEASE BE SURE THE NOTARY PLACES INFORMATION ON LETTER
 WHICH IS REQUIRED UNDER FS 117.05
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW THAT DUE TO THE EXTENT OF COMMENTS AND
 NATURE OF COMMENT,FOR ELECTRICALREVIEW AND FOR THAT
 OF OTHER REQUIREMENTS UNDER FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE, ONE SET OF PLANS SUBMITTED
 ARE BEING RETAINED BY THIS OFFICE.
  
 10) NOTE: PLEASE SEE TITLE BLOCK APPEARS TO SHOW
 COMPANY/FIRM AND NOT ONLY THE ARCHITECT AS AN
 INDIVIDUAL. PLEASE PROVIDE CERTIFICATE OF AUTHORIZATION
 NUMBER AS APPLICABLE UNDER FS 481.219, FA C61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]