Date |
Text |
2007-03-10 07:13:02 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. INDICATE THE CODE IN EFFECT FOR THE DESIGN OF THE |
| BUILDING ON THE PLANS. (FBC-2004 W/06 AMENDMENTS). |
| SECTION 106.1.2. |
| |
| 2. SHOW THE SQUARE FOOTAGE OF THE BUILDING ON THE |
| PLANS. SECTION 106.1.2. |
| |
| 3. SHT 1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN. THE FIXTURE LAYOUT OF THE RISER DOES |
| NOT REFLECT THE FIXTURE LAYOUT OF THE FLOOR PLAN AND |
| THE SERVICE SINK IS NOT INDICATED ON THE RISER |
| ISOMETRIC DIAGRAM. PLEASE CORRELATE THE RISER AND THE |
| FLOOR PLAN. SECTION 106.1.1. (SEE EXAMPLE OF A RISER |
| DIAGRAM THAT REFLECTS THE EXISTING FLOOR PLAN AS |
| SHOWN). |
| |
| 4. SHT 1 THE WATER RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. PLEASE CORRELATE THE RISER AND THE FLOOR |
| PLAN. SECTION 106.1.1. |
| |
| 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES. AS SHOWN |
| THERE APPROXIMATELY 1,158SSF NET DIVIDED BY 5 NET AS |
| INDICATED IN TABLE 1004.1.2 THERE ARE 232 OCCUPANTS. |
| PER TABLE 403.1 232 DIVIDED BY 2 EQUALS 116 MEN - 116 |
| WOMEN. DIVIDED BY 40 EQUALS 2.9 OR 3 WATER CLOSETS EACH |
| REQUIRED FOR MEN AND WOMEN, WITH 2 LAVS EACH FOR MEN |
| AND WOMEN. |
| |
| 6. ALL SHEETS, THE ADDRESS OF THE ARCHITECT IS REQUIRED |
| IN THE TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055. |
| (SEE ATTACHED SHEET). |
| |
| 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS |
| REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30" |
| WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE |
| SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE |
| DRINKING FOUNTAIN. |
| |
| 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE |
| 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR |
| FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE |
| WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION |
| 11-4.17.3 EXCEPTIONS (1)(2). |
| |
| 9. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE |
| LAVS: |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |