Plan Review Notes For Permit 07020129 |
Permit Number |
07020129 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-21 14:20:14 | *****DENIED***** | | | | | | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK | | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | SAID PROPERTY OR VICINITY THEREOF. | | | | 4.INDICATE THE OCCUPANT LOAD FOR THE PROPOSED | | STRUCTURE BASED UPON THE OCCUPANT LOAD FACTORS THAT ARE | | CHARACTERISTIC OF THE USE OF THE SPACE OR DETERMINED AS | | THE MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER | | CONSIDERATION, WHICHEVER IS GREATER. | | | | 5.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA | | HAVING AN OCCUPANT LOAD OF 100 OR MORE SHALL BE | | PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. | | | | 6.PLEASE PROVIDE A LAYOUT SHOWING THE ARRANGEMENT OF | | FURNISHINGS, TABLES, SEATS, AND(OR) EQUIPMENT. | | | | 7.SHOW THE LOCATION OF THE 2A10BC FIRE | | EXTINGUISHER(S). | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | |
|