2007-02-25 13:33:51 | *** UNSAT *** |
| |
| ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER |
| 05010378 WHICH BECAME *EXPIRED*. |
| |
| **PLEASE SEE MANY OF THE NOTES ARE THE SAME AS STATED |
| IN ORIGINAL REVIEWS AND NUMEROUS NEW COMMENTS DUE TO |
| CHANGES MADE TO PLANS WHICH WERE NOT ON PREVIOUS |
| REVIEWED PLANS AND NOTES FOR NEW CODE CHANGES. |
| |
| |
| 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| 8TH, 2006. |
| 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| SUBMITTED |
| 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE THERE ARE SECTIONS OF CODES REFERENCED |
| FROM THE 2002 NEC. |
| |
| 2) NOTE: PLEASE SEE THERE ARE NUMEROUS NOTES ON PLANS |
| WHICH REFERENCE ITEMS TO THIS BEING A RESIDENTIAL |
| DWELLING? PLEASE ADJUST ALL NOTES ACCORDINGLY. THIS |
| SCOPE OF WORK IS NOT FOR A RESIDENTIAL DWELLING. |
| |
| 3) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH PANEL SCHEDULE(S). |
| PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL |
| DO NOT SHOW THE CIRCUITING. |
| PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND |
| CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL |
| SCHEDULES SUBMITTED. |
| PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS; |
| HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL |
| RECEPTACLES FOR THIS UNIT. |
| PLEASE CORRELATE AND COORDINATE ALL. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE |
| PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE |
| ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. |
| PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR |
| RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION. |
| |
| 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS. |
| THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER |
| PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO |
| PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER |
| AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE, |
| NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE |
| CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. |
| THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. |
| |
| 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW |
| PER, 220.12, 220.14, 220.42, 220.44 ETC. |
| PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| 215.3, AND 230.42 |
| PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL |
| CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE |
| SUB PANEL *C*. |
| PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED |
| ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE |
| SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL |
| SCHEDULE(S). (SIGN CIRCUIT) |
| |
| 7) NOTE: PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS |
| NOW BEEN SUBMITTED AND IS MISSING INFORMATION NEEDED |
| FOR CODE COMPLIANCE AND FOR REVIEW. |
| PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN |
| THIS ONE COMMENT. |
| A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE |
| EQUIPMENT AND MAINS. |
| B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON |
| PLANS. |
| C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE |
| SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE |
| FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON |
| THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS. |
| PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS, |
| DIFFERENT OVER CURRENT PROTECTION ETC. |
| D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED |
| FOR SERVICE. |
| ETC. |
| 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC |
| PLEASE SEE 2005 NEC. |
| |
| 8) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| .1.2 AND .1.3. |
| PLEASE SUBMIT ENERGY CALCULATIONS PER THE 2004 FBC W/ |
| 2006 REVISION. PLEASE SEE ENERGY CALCULATIONS SUBMITTED |
| ARE FROM THE 2001 FBC. |
| PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| CALCULATIONS ALONG WITH ENERGY CALCULATIONS. PLEASE BE |
| SURE TO HAVE THE DESIGNER OF RECORD SIGN, DATE AND SEAL |
| THESE AS REQUIRED PER 13-103.1.1.1 |
| |
| 9) NOTE: PLEASE SEE FLORIDA STATUES 481.221 WHICH |
| REQUIRES TO THE ARCHITECT TO ALSO DATE PLANS WHEN |
| SIGNING AND SEALING SAID PLANS. |
| |
| 10) NOTE: PLEASE SEE PLANS SUBMITTED ARE IN FACT |
| COLORED PHOTO-COPIES OF PLANS STAMPED PREVIOUSLY BY THE |
| CITY ZONING REVIEWER AND PALM BEACH COUNTY FOR IMPACT |
| FEES. PLEASE KNOW THAT THESE SHALL BE ORIGINAL AND MAY |
| NOT MAKE CHANGES TO PLANS AND COLOR PHOTO-COPY PLANS. |
| PLANS WILL BE REQUIRED TO GO BACK TO HISTORIC, ZONING, |
| AND PALM BEACH COUNTY AS PERMIT APPLICATION IS NOW |
| UNDER NEW PALM BEACH COUNTY IMPACT FEE SCHEDULE AS OF |
| JAN 1ST, 2006. |
| |
| 11) NOTE: PLEASE SEE PLANS WHICH STILL STATE *CORAL KEY |
| DESIGN*. PLEASE KNOW AS PER FS481.229, A DESIGNER, |
| DRAFTING, CADD DESIGN COMPANY MAY NOT DESIGN PLANS |
| FORCOMMERICAL/ PUBLIC USE OF THIS NATURE. THIS HAS BEEN |
| CONFIRMED WITH THE STATE OF FLORIDA LEGAL COUNSEL TO |
| THE BOARD OF ARCHITECTS AND THIS COMMENT WAS MADE ON |
| PREVIOUS REVIEWS UNDER THE EXOIRED PERMIT. |
| FURTHER CONTACT MAY BE DONE WITH STATE PROSECUTOR |
| MR.DAVID MINACCI, OR STATE INVESTIGATOR MR. LES SMITH. |
| |
| 12) NOTE: PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES |
| AND OVER CURRENT PROTECTION DEVICES ON PANEL |
| SCHEDULES. |
| PLEASE SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,; |
| HOWEVER SEE LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE |
| 1-POLE 45AMP BREAKERS, SEE #8 AWG ON 20AMP BREAKERS, |
| SEE 30AMP BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC |
| ETC. |
| 240.4, 310.16 ETC. |
| SEE 2005 NEC. |
| |
| 13) NOTE: PLEASE SEE MISSING A/C UNITS AND THERE |
| REQUIRED DISCONNECTING MEANS PER 440.11. PLEASE SEE |
| MISSING CU DISCONNECT, PLEASE SEE MISSING AHU |
| DISCONNECT ETC. PLEASE SEE SOME SHOWN WITH A RECEPTACLE |
| FOR UNIT TO PLUG-IN WHICH IS PROHIBITED. |
| 422.30, 422.31, 440.11 ETC. |
| |
| 14) NOTE: PLEASE SEE AHU'S WITH OVER CURRENT PROTECTION |
| WHICH IS TOO HIGH FOR THE 5KW LOAD SHOWN. AHU'S #1 AND |
| #2. |
| 240.4, 310.16, AND FBC 106.1.2, 106.3.5.1.2 FOR |
| COORDINATION. |
| |
| |
| 15) NOTE: PLEASE KNOW THAT DUE TO THE EXTENT OF |
| COMMENTS AND NATURE OF COMMENT,FOR ELECTRICALREVIEW |
| AND FOR THAT OF OTHER REQUIREMENTS UNDER FLORIDA |
| STATUTES AND FLORIDA ADMINISTRATIVE CODE, ONE SET OF |
| PLANS SUBMITTED ARE BEING RETAINED BY THIS OFFICE. |
| |
| 16) NOTE: PLEASE SEE THAT THE NEWLARGER ADA BATHROOM |
| SHALL CONTAIN A BATTERY BACK UP LIGHTING FIXTURE FO |
| SOME TYPE. LS 101 7.8, 7.9. PLEASE CIRCUIT PER 700.12 |
| FO TEH NEC. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |