2007-03-13 10:08:12 | BUILDING PLAN REVIEW |
| PERMIT: 07020129 |
| ADD: 909 3RD ST |
| CONT: NEWBOLD CONSTRUCTION |
| TEL: (561)644-5764 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLY |
| COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| SUCH NOTICE IS |
| NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| OF COMMENCEMENT |
| AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| |
| 4) PLANS ARE COLOR COPIES, PLEASE CREATE ORIGINAL |
| DOCUMENTS, AND GET ORIGINAL SIGN-OFFS FROM THE VARIUOS |
| GOVERNMENTAL AGENCIES. |
| |
| 5) PLEASE PROVIDE THE UNITY OF TITLE FOR LOTS 12 & |
| 13.THE DOCUMENT SUBMITTED FOR REVIEW HAS NOT BEEN |
| SUBMITTED TO THE CLERK OFTHE COURT OF PALM BEACH |
| COUNTY. |
| ONCE RECORDED PLEASE PROVIDE DOCUMENTATION. |
| |
| 6)THE ENERGY CALCULATIONS SUBMITTED ARE ON THE |
| 2001FBC FORMS, THERE HAS BEEN CHANGES IN THE ENERGY |
| CODE AS WELLL AS THE ENERGY FORM SINCE THE 2001 FBC, |
| PLEASE CORRECT. |
| |
| 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS- SINGLE HUNG SUBMITTED REVISION# 2 STATE |
| WEBSITE ON CURRENT REVISION# 7. |
| ALSO HIGHLIGHT WHICH WINDOW SERIES |
| TO BE INSTALLED. |
| |
| B) EXTERIOR DOORS- THERMA-TRU DOORS FOR THE DOUBLE |
| DOORS TO MEET THE WIND PRESSURE REQUIRES A HIGH RISE |
| THRESHOLD, PLEASE SEE 1008.1.6, WHICH ALINE WITH |
| ACCESSIBLITY REQUIREMENTS. |
| 1008.1.6 THRESHOLDS. |
| THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 0.75 INCH (19.1 |
| MM) IN HEIGHT FOR SLIDING DOORS SERVING DWELLING UNITS |
| OR 0.5 INCH (12.7 MM) FOR OTHER DOORS. RAISED |
| THRESHOLDS AND FLOOR LEVEL CHANGES GREATER THAN 0.25 |
| INCH (6.4 MM) AT DOORWAYS SHALL BE BEVELED WITH A SLOPE |
| NOT GREATER THAN ONE UNIT VERTICAL IN TWO UNITS |
| HORIZONTAL (50-PERCENT SLOPE). |
| |
| C) ROOFING ASSEMBLIES, STATE APPROVAL FOR OWENS CORNING |
| ASPHALT SHINGLES,ARE NOT ON REVISION # 1 NO LONGER, |
| ALSO THE REPORT SUBMITTED IS A MIAMI-DADE REPORT NUT A |
| UL-REPORT. PLEASE PROVIDE THE APPROPRIATE REPORT , |
| STARTER INFORMATION + INFORMATION FOR 3 TAB . |
| |
| 8)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |