Plan Review Notes
Plan Review Notes For Permit 07020123
Permit Number 07020123
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-05 18:58:32BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF NOA 02-0212.07 SUBMITTEDIS MISSING THE
 SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED AS REQUIRED
 BY CITY POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY
 OF CITY POLICY.
  
 2- IF SELECTED ASSEMBLY HAS MORE THAN ONE FASTENING
 OPTION FOR BASE SHEET, THEN CLEARLY IDENTIFYWHICH
 OPTION WILL BE USED.SEE ROOFING POLICY.
  
 3- IF SELECTED ASSEMBLYIS LIMITED BY GENERAL
 LIMITATION #7, THEN NEED TO PROVIDERAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS.NOA 02-0212.07 SUBMITTED REQUIRES CALCULATIONS
 TO BE DONE ONLY BY ARCHITECT, ENGINEER OR REGISTERED
 ROOFING CONSULTANT. SEE GENERAL LIMITATIONS ON LAST
 PAGE OF NOA.
  
 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE INSTALLED IN THIS AREA
 BECAUSE NAIL ENHANCING IS NOT ALLOWED AND APPROVED
 ASSEMBLIES DON'T MEET THE DESIGN PRESSURES OF TABLE
 1609.6.2.1(2). SEE GENERAL LIMITATIONS ON LAST PAGE OF
 THE NOA.
  
 5- A) PERMIT APPLICATION SCOPE OF WORKDOESN'T INCLUDE
 THE SKYLIGHTS. INCLUDE THEM ONLY IF WORK IS TO REPLACE
 EXISTING SKYLIGHTS.NEW SKYLIGHTS ON NEW OPENINGS
 REQUIRE SEPARATE PERMIT BY PROPER CONTRACTOR.
 B) IF REPLACING SKYLIGHTS, THEN SPECIFY HOW MANY
 AND INCLUDE THEM IN TOTAL BUILDING VALUATION. IF
 DECLARE VALUATION IS TOO LOW, THEN IT WILL BE UPDATED
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 C) PROVIDE LEGIBLEDRAWINGS FOR THE SKYLIGHTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712