Plan Review Notes For Permit 07020122 |
Permit Number |
07020122 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-01 16:12:29 | | | DENIED/INCOMPLETE INFORMATION | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE FEEDER TO PANEL 'B' IS LISTED AS #4 IN PANEL | | "A", AND SHOWN AS #1 ON THE RISER. CORRELATE SAME. | | | | 2} INDICATE WHAT "WT" MEANS LISTED AFTER THE LOADS. | | | | 3} THE AIR HANDLER LOCATED IN THE CLOSET, HAVING | | OVERCURRENT PROTECTION BUILT IN, IS IN VIOLATION OF | | 240.24(B), 2005NEC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|