Plan Review Notes
Plan Review Notes For Permit 07020122
Permit Number 07020122
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-11 16:49:23BUILDING REVIEW SECOND CHECKLIST:
 1- BRING DRAWINGS TO PALM BEACH COUNTY (2300 N. JOG RD.
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE OR
 NOT.BRING BACKSTAMPED PLANS BY PALM BEACH COUNTY
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEE ATTACHED
 LEGAL FORM.
  
 3- SOIL TEST REPORT NEEDS TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 4- SHEET 2:
 A) SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING ATTIC
 LIVE LOADS,AS REQUIRED BY SEC. R301 AND TABLE R301.5
 OF 2004 FLORIDA RESIDENTIAL CODE (WITH 2006
 REVISIONS).
 ***CLARIFY WHY DEAD LOADS SPECIFIIED ON ROOF FRAMING
 PLAN ARE LARGER THAN THE LIVE LOADS. PROVIDE COMPLETE
 ENGINEERING ANALYSIS TO SHOW WHY THIS DESIGN CRITERIA
 WAS USED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) TRUSS ANCHOR SCHEDULE IS CONFUSING.IS NOT CLEAR
 WHICH ARE CONNECTORS'A'AND WHICH ARE CONNECTORS
 'B'.THEY ARE SHOWN ON THE LEFT HAND SIDE, BUT
 CONNECTORS SPECIFIED ON THE PRODUCT CODE COLUMN DON'T
 SHOW ANY RELATION TO CONNECTOR 'A' OR 'B'.
 REVISE/CLARIFY AS REQUIRED. SEC. 106.1L.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C)NUMBER OF FASTENERSAND LOADS SHOWN ON TRUSS
 ANCHOR SCHEDULE DON'T MATCH INFORMATION SHOWN ON
 PRODUCT APPROVAL SUBMITTED FOR THIS TYPE OF CONNECTORS.
 SEE PRODUCT APPROVAL AND REVISE AS REQUIRED. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR NUMBER OF
 FASTENERS AND LOADS THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 D) HANDWRITTEN INFORMATION SHOWN ON VALLEY TRUSSES
 IS NOT CLEAR.SPECS : "TS12/W 7-8D TO THE THE TRUSS
 AND 7-8D TO EXISTINGEACH END END TYP" IS NOT CLEAR.
 REVISE AS REQUIRED OR PROVIDE CLEAR DETAIL. AND,
 HANDWRITTEN INFORMATION ON PLANS IS NOT ACCEPTABLE.
 REVISE INFORMATION ON ORIGINAL CAD DRAWING.
  
 E) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. NEED
 MIN. 8D RING SHANK NAILS IN ALL ZONES. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 F)INFORMATION ON ITEM 4(E)NEED TO MATCH
 INFORMATION ONTYPICAL WALL SEC.REVISE AS REQUIRED.
  
 G) INFORMATION FOR GABLE ENDS AND WOOD FRAME WALLS
 IS NOT CLEAR.CLARIFY ASREQUIRED OR OMIT TO AVOID
 CONFLICTS SINCE PROPOSED ROOF DOESN'T HAVE GABLE ENDS.
  
 H) SPECIFY CONNECTORSFOR WOOD TRUSSES RESTING ON
 EXISTING BEARING WALL.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ASPHALT SHINGLES. NOA 02-1209.10 SUBMITTED IS
 CLOSED BY DADE COUNTY. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BYSEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- ENERGY CALCULATIONS:
 A) EXTERIORINSULATION VALUEDOESN'T MATCH
 INFORMATION ON PLANS. REVISE AS REQUIRED.
  
 B) SEE SURVEY FOR CORRECT HOUSE ORIENTATION AND
 REVISE AS REQUIRED.
  
 C) NUMBER OF AND SIZE OF WINDOWS DON'TMATCH PLANS.
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINE(561)805-6712