2007-03-07 14:10:33*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R
 (2004) PER FBC 13-600.3.A .
  
 2) SEE A/CPLAN PAGE 2 OF 4 EQUIPMENT SCHEDULE, "SEE"
 DO YOU MEAN SEER IF SO THE MINIMUM SEER THAT MAY BE
 INSTALLED IS 13 SEER, SEE 2004 FBC 13-607.1.ABC.3.2.1.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.