2007-03-06 15:02:37 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 3} THE AIR HANDLER LOCATED IN THE CLOSET, HAVING
 OVERCURRENT PROTECTION BUILT IN, IS IN VIOLATION OF
 240.24(B), 2005NEC.
  
 4} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, FOR THE CONDENSING
 UNIT.
  
 5} A SMOKE ALARM MUST BE LOCATED OUTSIDE THE "NEW
 FLORIDA ROOM" , A SLEEPING AREA BY DEFINITION.THE ONE
 SHOWN IN THE HALL IS NOT "OUTSIDE, AS IT IS IN THE SAME
 AREA WITH THE DOOR SHUT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER