Plan Review Notes
Plan Review Notes For Permit 07020122
Permit Number 07020122
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-26 18:00:32BUILDING REVIEW CHECKLIST:
 1- BUILDING VALUATION DECLARED ON PERMIT APPLICATION IS
 TOO LOW.VALUE WAS UPDATED. OWES $630.39 FOR UPDATED
 VALUE AND RADON FEES.
  
 2- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY AT 2300 N. JOG RD TO PAY IMPACT FEES. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- PROVIDE SOIL TEST REPORT.
  
 5- SHEET 1:
 A) NORTH ARROW IN SITE PLAN IS POINTING TO THE WRONG
 DIRECTION. SEE SURVEY AND REVISE AS REQUIRED.
  
 B) FOUNDATION WALL DOESN'T SHOW VERTICAL
 REINFORCEMENT IN NORTH AND SOUTH WALL. PROVIDE
 ENGINEERING CALCULATIONS SHOWING WHY REINFORCEMENT IS
 NOT REQUIRED FOR LATERAL SUPPORT. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) FOUNDATION PLAN DOESN'T INDICATE WHICH COLUMN IS
 C-1 AND WHICH IS C-2.ALSO, CLARIFY IF COLUMN C-2 IS
 CONCRETE BLOCK WITH FILLED CELL OR TRUE CAST IN PLACE
 CONCRETE COLUMN.DRAWING SHOW CONCRETE BLOCK WITH
 FILLED CELL. WHILE SPECS CALL FOR CAST IN PLACE
 CONCRETE COLUMN. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 D) CLARIFY SPECS FOR COLUMN C-1: IT'S NOT CLEAR WHY
 CALLING FOR DOWELS AT 4'-8" O.C. INTO EXISTING SLAB IF
 ALL THIS IS NEW CONSTRUCTION?
  
 E) NOTE #4 SAYS "NO A/C WITHIN THE SCOPE OF THIS
 PROJECT" BUT FLOOR PLAN ON SHEET 2 SPECIFIES A/C WORK.
 CLARIFY/REVISE AS REQUIRED.
  
 6- SHEET 2:
 A) SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 B) SPECIFY SAFETY GLASS FOR WINDOW IN SHOWER AREA.
 SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: SAFETY GLASS IS REQUIRED NEXT TO THE EXTERIOR
 DOOR IF WINDOW IS WITHIN 24" OF THE DOOR. SEE SEC.
 R308.4 ABOVE.
  
 C) SPECIFY ALL LIVE AND DEAD LOADS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE AND TABLE
 R301.5.
  
 D) SECOND STRUCTURAL NOTE CALLS FOR 40' (FEET?) MIN.
 LENGTH FOR SPLICING. REVISE AS REQUIRED.
  
 E) SIMPSON CONNECTORS A AND B. SEE CURRENT CATALOG
 FOR SPECIFIC NUMBER OF FASTENERS TO BE USED. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR FASTENERS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 F) REVISE PLYWOOD SHEATHING NAILING SCHEDULE AND
 ASTERISK NOTE. SEE SEC. R803.2.3.1OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 G) REVISE ROOF SKETCH SHOWING ROOF ZONES. SEE FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 ZONES ON HIP ROOF.
 ***NOTE: SPECIFY DIMENSION A FOR WITH OF ZONES THAT
 APPLY TO THIS PROJECT.SEC. R301 2004 FLORIDA
 RESIDENTIAL CODE.
  
 H) ANCHOR VALLEY TRUSSES.THESE TRUSSES ARE
 DESIGNED WITH CONTINUOUS UPLIFT LOADS AT BOTTOM CHORD,
 NOT AT THE ENDS OF TRUSS. SEE TRUSS DRAWINGS AND REVISE
 CONNECTORS AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 7- SHEET 3:
 A) PROVIDE ACTUAL CALCULATIONS FOR DESIGN PRESSURES
 AT DOORS AND WINDOWS. SOME OF THESE OPENINGS ARE
 LOCATED ON END ZONES, THEREFORE DESIGN PRESSURES ARE
 HIGHER. SEE TABLER301.2(2) OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) DESIGN CERTIFICATION FOR BUILDING CODE COMPLIANCE
 INFORMATION NEEDS TO BE UPDATED:
 * CODE EDITION 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC.
 ** ASCE 7-02, NOT ASCE 7-98.
 *** SPECIFY BUILDING EXPOSURE. SEE SEC. R301 OF 2004
 FLORIDA RESIDENTIAL CODE.
 **** SOIL BEARING CAPACITY: EXISTING?
 ***** IMPACT PROTECTION. THERE IS NOT IMPACT GLASS
 SPECIFIED ON PLANS.
  
 8- SHEET 4:
 A) ALL DRAWINGS AND SPECIFICATIONS FOR STRUCTURAL
 BUCK DETAILS AT DOORS AND WINDOWS TO MATCH. SEE ANCHOR
 TYPE AND SPACING.
  
 B) SEE SEC. R613.6.2 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR PROPER WAY OF INSTALLING STRUCTURAL BUCKS.
 BUCKS NEED TO PROVIDE COMPLETE SUPPORT OF WINDOW/DOOR
 FRAME.
  
 C) TYPICAL WALL SECTION:
 * REVISE ROOF SHEATHING SPECS.
 ** THERE IS NO SUPPORT SHOWN TO RECEIVE THE PLYWOOD
 SOFFIT.
 *** CLARIFY SPECS FOR 2X4 SUB FASCIA. FASTEN
 W/12-16D NAILS?
 **** SPECIFY FIREBLOCKING AS REQUIRED BY SEC.
 R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***** REVISE NOTE REGARDING #5 EMBEDEMNT ON EXISTING
 SLAB. THIS IS ALL NEW CONSTRUCTION.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) EXTERIOR DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED ON PLANS. . CHECK DESIGN PRESSURES AFTER
 DESIGN PRESSURES ARE REVISED ON PLANS.
  
 B) ASPHALT SHINGLES. NOA #02-1209.10 SUBMITTED FILE
 IS CLOSED. SEE ATTACHED COPY OF DADE COUNTY WEBSITE.
  
 C) SINGLE HUNG WINDOW NOA #02-0604.03 SUBMITTED FILE
 IS CLOSED ALSO.
  
 D) WINDOW MULLIONS.
  
 E) TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- STORM SHUTTERS. PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION SCHEDULE.
 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 PRODUCT APPROVAL.
  
 12- ENERGY CALCULATIONS:
 A) NEED TO USE 2004 FORM.
  
 B) SLAB ON GRADE INSULATION AND TOTAL PERIMETER
 DIMENSION AREWRONG. REVISE AS REQUIRED. SEE PLANS.
  
 C) MINIMUM SEER REQUIRED IS 13. REVISE AS REQUIRED.
  
 D) SEE SURVEY FOR CORRECT HOUSE CARDINAL ORIENTATION
 AND REVISE AS REQUIRED.
  
 E) OVERHANG HEIGHT AND LENGTH IS INCORRECT. REVISE
 AS REQUIRED.
  
 F) WALL EXTERIOR INSULATION IS WRONG. SEE PLANS AND
 REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712