Plan Review Notes
Plan Review Notes For Permit 07020065
Permit Number 07020065
Review Stop M
Sequence Number 2
Notes
Date Text
2007-05-17 14:13:10*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SUBMIT COOLING LOAD CALCULATIONS, SEE
 13-607.1.ABC.1.
  
 3) SHOW ON A/C PLANS EQUIPMENT SCHEDULE CONDENSER UNIT
 MODEL NUMBER AND HEATER KW.
  
 4) SHOW THE SIZE OF THE SUPPLY AIR DUCT ON THE FIRST
 FLOOR TRUNK LINE TO THE MIXING BOX (SEE YELLOW HIGH
 LIGHT ON PLANS).
  
 5) THE WATER CLOSET ROOM AT THE MASTER SUITE WILL NEED
 AN EXHAUST FAN, SEE 2004 FBC/R M1506.3.
  
 6) THE 12" RETURN AIR TRANSFER TO THE MASTER SUITE
 NEEDS TO BE 18", SEE 2004 FBC/R M1602.4.
  
 ALL OF THESE CORRECTIONS HAVE BEEN REQUESTED ON OTHER
 IDENTICAL HOMES FOR ROSEMARY ACQUISITIONS SUBMITTED TO
 THIS OFFICE BY SCOTCORP INC.. IN THE FUTURE PLEASE
 CHECK AND CORRECT PLANS FOR THESE SAME JOBS BEFORE
 SUBMITTING FOR PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.