2007-05-29 14:30:35 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2- PAY IMPACT FEES TO PALM BEACH COUNTY.BRING BACK |
| STAMPED PLANS AND COPY OF PAID RECEIPT. |
| |
| 3- OWES $2527.82 FOR UPDATED VALUATION, RADON FEES AND |
| OUTSTANDING BALANCE AT TIME OF PERMIT APPLICATION. |
| |
| 4- ENERGY CALCULATIONS: |
| A) REVISE OVERHANG HEIGHT AND OVERHANG LENGTH. SEE |
| PLANS AND REVISE AS REQUIRED. |
| |
| B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| INCLUDING BUILDER INFORMATION. |
| |
| C) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM. |
| |
| 5- PROVIDE COMPLETE INFORMATIONFOR STORM SHUTTERS. |
| PROVIDEPRODUCT APPROVAL AND COMPLETE INSTALLATION |
| SCHEDULE.SEE ATTACHED SAMPLE.ALSO,CIRCLE ON STORM |
| SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS, |
| SPECIFIC ANCHOR TYPE AND SPACING ACCORDING TO THE |
| DESIGN PRESSURES, EDGE DISTANCE, CONNECTION TYPE AND |
| STRUCTURE TO BE ATTACHED TO (CONCRETE BLOCK OR |
| CONCRETE). SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| ***NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE (NOT |
| SIGNING AND SEALIING)IN WRITING ALL PRODUCT APPROVALS |
| AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| 6-A) SURVEY DOESN'T MATCH FLOOR PLANS. |
| |
| B) CLARIFY WHICH LOT IS GOING TO BE BUILT, LOT 8 OR |
| 9.REVISE INFORMATION WITH PERMIT CLERK. |
| |
| C) CONTACT LILYAT (561)822-1239 TO CLARIFY CORRECT |
| LOT, PARCEL ID AND HOUSE NUMBER. |
| |
| D) PROPERTY IS LOCATED ON FLOOD ZONE "B", NOT"C". |
| REVISE SURVEY AS REQUIRED. |
| |
| 7- A)REVISE PLYWOODSHEATHING NAILING SCHEDULE ON |
| SHEET S-3.SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| |
| B) ALSO, REVISE NOTE REGARDING RING SHANK NAILS NOT |
| REQUIRED FOR MEAN ROOF HEIGHTS LESS THAN 25'-0" HIGH. |
| SEE SEC. ABOVE AND REVISE AS REQUIRED. |
| |
| |