Plan Review Notes
Plan Review Notes For Permit 07020059
Permit Number 07020059
Review Stop M
Sequence Number 2
Notes
Date Text
2007-05-10 12:07:55*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) COOLING LOAD CALCULATIONS ARE MISSING FROM ENERGY
 CAL'S. PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE
 2004 FBC 13-607.1.ABC.1.
  
 3) A/C EQUIPMENT LISTING ON PLANS DOES NOT SHOW
 INFORMATION REGARDING THE CONDENSER UNIT, PLEASE ADD
 THAT INFORMATION TO PLANS.
  
 4) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT, PLEASE CORRECT.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.