Plan Review Notes For Permit 07020059 |
Permit Number |
07020059 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-05-10 12:07:55 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) COOLING LOAD CALCULATIONS ARE MISSING FROM ENERGY | | CAL'S. PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE | | 2004 FBC 13-607.1.ABC.1. | | | | 3) A/C EQUIPMENT LISTING ON PLANS DOES NOT SHOW | | INFORMATION REGARDING THE CONDENSER UNIT, PLEASE ADD | | THAT INFORMATION TO PLANS. | | | | 4) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE | | NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C) | | EXCEPT, PLEASE CORRECT. | | | | *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|