Date |
Text |
2007-05-01 10:00:55 | *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| |
| 2) ENERGY CALCULATIONS, CONSERVATION CREDITS SHOW |
| DEDICATED HEAT PUMP BEING INSTALLED, ELECTRICAL PLANS |
| SHOW AN ELECTRIC HEATER BEING INSTALLED, MECHANICAL |
| PLANS SHOW NO HEAT BEING INSTALLED, PLEASE CORRECT SO |
| ALL THREE ARE THE SAME. |
| |
| 3) MECHANICAL PLANS EQUIPMENT LISTING NEED CONDENSER |
| UNIT MODEL NUMBER, ELECTRIC HEATER KW, IF HEAT PUMP |
| UNIT PLEASE STATE SO ON PLANS SO SEER MAY BE VERIFIED |
| WITH THE ARI DIRECTORY. |
| |
| 4) SEE MECHANICAL PLANS SHOW THE MASTER BATHROOM |
| EXHAUST FAN OUTSIDE OF THE WATER CLOSET ROOM, IF TWO |
| ARE BEING INSTALLED ADD ONE TO WATER CLOSET ROOM, IF |
| NOT MOVE TO WATER CLOSET ROOM. |
| |
| 5) SUPPLY AIR DUCT (FLEX) TO MIXING BOX FIRST FLOOR |
| FAMILY ROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT ON |
| MECHANICAL PLANS. |
| |
| 6) 12" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS |
| TO BE 16", SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT. |
| PLEASE CORRECT. |
| |
| ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |