2007-05-01 10:00:55*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) ENERGY CALCULATIONS, CONSERVATION CREDITS SHOW
 DEDICATED HEAT PUMP BEING INSTALLED, ELECTRICAL PLANS
 SHOW AN ELECTRIC HEATER BEING INSTALLED, MECHANICAL
 PLANS SHOW NO HEAT BEING INSTALLED, PLEASE CORRECT SO
 ALL THREE ARE THE SAME.
  
 3) MECHANICAL PLANS EQUIPMENT LISTING NEED CONDENSER
 UNIT MODEL NUMBER, ELECTRIC HEATER KW, IF HEAT PUMP
 UNIT PLEASE STATE SO ON PLANS SO SEER MAY BE VERIFIED
 WITH THE ARI DIRECTORY.
  
 4) SEE MECHANICAL PLANS SHOW THE MASTER BATHROOM
 EXHAUST FAN OUTSIDE OF THE WATER CLOSET ROOM, IF TWO
 ARE BEING INSTALLED ADD ONE TO WATER CLOSET ROOM, IF
 NOT MOVE TO WATER CLOSET ROOM.
  
 5) SUPPLY AIR DUCT (FLEX) TO MIXING BOX FIRST FLOOR
 FAMILY ROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT ON
 MECHANICAL PLANS.
  
 6) 12" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS
 TO BE 16", SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT.
 PLEASE CORRECT.
  
 ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.