2007-05-08 11:31:37BUILDING REVIEW SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- NEED TO PAY IMPACT FEES TO PALM BEACH COUNTY AND
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- ENERGY CALCULATIONS:
 A) OVERHANG LENGHT AND OVERHANG HEIGHT ARE
 INCORRECT. SEEELEVATIONS AND REVISE AS REQUIRED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME.
  
 C) ARCHITECT SIGNING ENERGY CALCULATIONS NEED TO
 PROVIDE HIS SEALAS REQUIRED BY SEC. 481 FLORIDA
 STATUTE AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G1-16.003.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 4- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS,
 INCLUDING PRODUCT APPROVAL, KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE.
 ***NOTE:DESIGNER OF RECORD TO REVIEW AND APPROVE
 PRODUCT APPROVAL PRIOR TO SUBMITTAL.
  
 5- OWES $2527.82 FOR BUILDING VALUATION UPDATE, RADON
 FEES AND BALANCE DUE BECAUSE TOTAL PERMIT APPLICATION
 FEE WAS NOT PAID AT TIME OF PERMIT APPLICATION.
  
 6-ONE OF THE GARAGE DOORS PRODUCT APPROVALS IS
 MISSING THE ARCHITECT'S REVIEW STAMP. COMPLETE AS
 REQUIRED.
  
 7- SHEET A-4.1:
 A) CLARIFY DETAIL #1. IT'S THIS DETAIL FOR WINDOW OR
 DOOR. TITLE SAYS FOR WINDOW,WHILE DETAILSAYS FOR
 DOOR.
 ON THE OTHER HAND DETAIL DOESN'T MATCH SPECS SHOWN ON
 STRUCTURAL DRAWINGS. REVISE AS REQUIRED.
  
 B) HURRICANE PANEL DETAIL: EDGE DISTANCE IS MEASURED
 WRONG. REVISE AS REQUIRED.
 ***NOTE:THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND
 LESS CONFUSING IF SUBMITTING ONLY THE PRODUCT APPROVAL
 FOR STORM SHUTTERS ALONG WITH COMPLETE INSTALLATION
 SCHEDULE.
  
 8- SHEET S-3:
 A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MINIMUM SIZE AND TYPE OF NAIL TO BE USED.
 ALSO, DELETE NOTE REGARDING RING SHANK NAILS NOT
 REQUIRED IFMEAN ROOF HEIGHT IS LESS THAN 25'.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712