2007-05-08 11:31:37 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2- NEED TO PAY IMPACT FEES TO PALM BEACH COUNTY AND |
| BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT. |
| |
| 3- ENERGY CALCULATIONS: |
| A) OVERHANG LENGHT AND OVERHANG HEIGHT ARE |
| INCORRECT. SEEELEVATIONS AND REVISE AS REQUIRED. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. |
| |
| C) ARCHITECT SIGNING ENERGY CALCULATIONS NEED TO |
| PROVIDE HIS SEALAS REQUIRED BY SEC. 481 FLORIDA |
| STATUTE AND FLORIDA ADMINISTRATIVE CODE SEC. |
| 61G1-16.003. |
| |
| D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| 4- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS, |
| INCLUDING PRODUCT APPROVAL, KEY PLAN AND A COMPLETE |
| INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE OF |
| INSTALLATION SCHEDULE. |
| ***NOTE:DESIGNER OF RECORD TO REVIEW AND APPROVE |
| PRODUCT APPROVAL PRIOR TO SUBMITTAL. |
| |
| 5- OWES $2527.82 FOR BUILDING VALUATION UPDATE, RADON |
| FEES AND BALANCE DUE BECAUSE TOTAL PERMIT APPLICATION |
| FEE WAS NOT PAID AT TIME OF PERMIT APPLICATION. |
| |
| 6-ONE OF THE GARAGE DOORS PRODUCT APPROVALS IS |
| MISSING THE ARCHITECT'S REVIEW STAMP. COMPLETE AS |
| REQUIRED. |
| |
| 7- SHEET A-4.1: |
| A) CLARIFY DETAIL #1. IT'S THIS DETAIL FOR WINDOW OR |
| DOOR. TITLE SAYS FOR WINDOW,WHILE DETAILSAYS FOR |
| DOOR. |
| ON THE OTHER HAND DETAIL DOESN'T MATCH SPECS SHOWN ON |
| STRUCTURAL DRAWINGS. REVISE AS REQUIRED. |
| |
| B) HURRICANE PANEL DETAIL: EDGE DISTANCE IS MEASURED |
| WRONG. REVISE AS REQUIRED. |
| ***NOTE:THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND |
| LESS CONFUSING IF SUBMITTING ONLY THE PRODUCT APPROVAL |
| FOR STORM SHUTTERS ALONG WITH COMPLETE INSTALLATION |
| SCHEDULE. |
| |
| 8- SHEET S-3: |
| A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS. SEE |
| SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR |
| MINIMUM SIZE AND TYPE OF NAIL TO BE USED. |
| ALSO, DELETE NOTE REGARDING RING SHANK NAILS NOT |
| REQUIRED IFMEAN ROOF HEIGHT IS LESS THAN 25'. |
| |