| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT |
| SATISFY THIS REQUIREMENT. |
| |
| 2} THE REFERENCE TO THE 2002 NEC IS ALSO INCORRECT IN |
| THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA |
| LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION |
| FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE |
| SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO |
| REFLECT THIS CHANGE. |
| |
| 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE |
| ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY |
| ROUTE OVERHEAD THROUGH THE GARAGE, THEN A MAIN |
| DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1). |
| IF THEY ARE UNDER THE SLAB THE MAIN IN THE PANEL WOULD |
| BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE DISCONNECT IF |
| NECESSARY. |
| |
| 4} A RECEPTACLE IS REQUIRED IN THE 2ND FLOOR HALL PER |
| 21052(E). |
| |
| 5} THE WATER HEATER CIRCUIT 21,23, IS LISTED AS A 30 |
| AMP SINGLE POLE IN THE SCHEDULE, PLEASE CORRECT. |
| |
| WILLIAM R. TROBAUGH |
| ELECTRICAL PLANS EXAMINER |