 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT
 SATISFY THIS REQUIREMENT.
  
 2} THE REFERENCE TO THE 2002 NEC IS ALSO INCORRECT IN
 THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA
 LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION
 FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE
 SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO
 REFLECT THIS CHANGE.
  
 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE
 ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY
 ROUTE OVERHEAD THROUGH THE GARAGE, THEN A MAIN
 DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1).
 IF THEY ARE UNDER THE SLAB THE MAIN IN THE PANEL WOULD
 BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE DISCONNECT IF
 NECESSARY.
  
 4} A RECEPTACLE IS REQUIRED IN THE 2ND FLOOR HALL PER
 21052(E).
  
 5} THE WATER HEATER CIRCUIT 21,23, IS LISTED AS A 30
 AMP SINGLE POLE IN THE SCHEDULE, PLEASE CORRECT.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT