2007-05-29 16:48:12 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT.SEC. 713.13 |
| FLORIDA STATUTE. |
| |
| 2- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK |
| STAMPED PLANS AND COPY OF PAID RECEIPT. |
| |
| 3- ENERGY CALCULATIONS: |
| A) REVISE OVERHANG HEIGHT AND OVERHANG LENGTH. IT |
| CAN'T BE ZERO. SEE PLANS AND REVISE AS REQUIRED. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. |
| |
| 4- IF TAKEN CEILING FANS CREDIT, THENPLANS NEED TO |
| SHOW CEILING FAN SIZE TO COMPLY WITH TABLE 13-607.1.A.1 |
| OF FBC 2004. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE. ALSO, CIRCLE ON |
| ENGINEERED DRAWINGS SPECIFIC MOUNTING CONDITIONS AND |
| SPECIFIC ANCHOR TYPE AND SPACING TO BE USED ACCORDING |
| TO THE DESIGN PRESSURES, EDGE DISTANCE,MAXIMUM PANEL |
| SPAN,CONNECTION TYPE AND STRUCTURE TO BE ATTACHED TO |
| (CONCRETE BLOCK OR CONCRETE). |
| |
| *** NOTE; DESIGNER OF RECORD TO REVIEW AND APPROVE IN |
| WRITING PRODUCT APPROVAL PRIOR TO SUBMITTAL. SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 6- OWES $646.64 FOR UPDATED VALUATION AND RADON FEES. |
| |
| 7- SHEET 7.1: REVISE WALL SECTION 2/7.1. HOW CAN ANCHOR |
| BOLT FOR (2)2X8 LEDGER BE EMBEDED 6" IF ANCHOR |
| SPECIFIED IS 5/8" X 3 1/2" LONG ?. REVISE AS REQUIRED. |
| |
| 8- SHEET 9.1: CLARIFY HOW EGRESS WINDOWS HAVE DIFFERENT |
| CLEAR AREA IF THEY ARE THE SAME SIZE?. SEE WINDOWS D, |
| G,M AND Q AND REVISE AS REQUIRED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |